Capacity Ratings - Carrier GEMINI SELECT 38APS025-065 Product Data

Commercial air-cooled condensing units with puron refrigerant (r-410a) 50/60 hz
Hide thumbs Also See for GEMINI SELECT 38APS025-065:
Table of Contents

Advertisement

Capacity ratings

CAPACITY
UNIT SIZE
NOMINAL TONS
(60 Hz)
38APS025
24.0
38APD025
24.0
38APS027
26.6
38APD027
26.6
38APS030
31.1
38APD030
31.1
38APS040
39.8
38APD040
39.2
38APS050
48.1
38APD050
50.0
38APD060
58.3
38APS065
59.6
38APD070
67.3
38APD080
78.0
38APD090
87.4
38APD100
96.0
38APD115
110.4
38APD130
125.1
LEGEND
EER — Energy Efficiency Ratio
IPLV — Integrated Part Load Value
38AP UNIT CAPACITY RATINGS
CAPACITY
CAPACITY
NOMINAL kW
NOMINAL TONS
(60 Hz)
(50 Hz)
84.3
19.9
84.3
19.9
93.4
22.1
93.4
22.1
109.2
25.8
109.2
25.8
139.8
33.0
137.7
32.5
168.9
39.9
175.6
41.5
204.7
48.4
209.6
49.4
236.4
55.9
273.9
64.7
306.9
72.5
337.2
79.7
388.3
91.6
440.0
103.8
CAPACITY
EER
NOMINAL kW
(60 Hz)
(50 Hz)
69.9
11.0
69.9
11.0
77.6
10.9
77.6
10.9
90.6
10.8
90.6
10.8
115.9
11.6
114.1
11.5
140.1
11.1
145.7
10.8
170.0
11.1
173.7
11.0
196.3
11.0
227.2
11.1
254.6
11.3
279.9
11.1
322.1
11.2
365.0
11.0
NOTES:
1. Unit performance is rated in accordance with ARI (Air Conditioning
and Refrigeration Institute) Standard 365.
2. Ratings are based on 45 F (7.2 C) saturated suction temperature
and 95 F (35 C) outside-air temperature, and include suction line
losses.
EER
IPLV
IPLV
(50 Hz)
(60 Hz)
(50 Hz)
11.6
14.4
15.5
11.6
13.1
14.1
11.5
14.7
15.7
11.5
14.0
14.7
11.4
14.3
15.2
11.4
12.8
13.6
12.1
16.2
17.4
12.0
15.3
16.4
11.7
15.0
15.9
11.3
14.9
15.9
11.7
14.5
15.5
11.6
15.1
16.1
11.4
15.7
16.7
11.5
15.6
16.6
11.8
15.3
16.4
11.6
15.0
16.0
11.7
15.2
16.2
11.5
15.2
16.2
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gemini select 38apd025-130

Table of Contents