Carrier 38APD025-130 Installation Instructions

Long line check valve accessory
Hide thumbs Also See for 38APD025-130:

Advertisement

Part No.: 38AP-900---011, 38AP-900---012, 38AP-900---013
SAFETY CONSIDERATIONS
When installing this accessory, observe precautions in the
literature and on any labels attached to the equipment, and all
other safety precautions that may apply.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling and installing this accessory.
WARNING
To avoid the possibility of electrical shock, open and tag all
disconnects before installing this equipment. Failure to do
so could result in severe personal injury.
INTRODUCTION
An accessory long line check valve must be installed for:
1. Any 025-030 size dual circuit unit where the evapora-
tor is located higher than the condensing unit and the
linear line length exceeds 55 ft (16.8 m).
2. Any size dual or single circuit unit with linear line
length of 100 ft (30.5 m) or more.
UNIT
CIRCUIT
SIZE
TYPE
Dual
38APD/S025
Single
Dual
38APD/S027
Single
Dual
38APD/S030
Single
Dual
38APD/S040
Single
Dual
38APD/S050
Single
38APD060
Dual
38APS065
Single
38APD070
Dual
38APD080
Dual
38APD090
Dual
38APD100
Dual
38APD115
Dual
38APD130
Dual
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53380009-01
Long Line Check Valve Accessory

Installation Instructions

ACCESSORY USAGE
CHECK
VALVE SIZE
(in. ODF)
5/8 + 5/8
5/8
5/8 + 5/8
5/8
5/8 + 5/8
7/8
5/8 + 5/8
7/8
5/8 + 5/8
7/8
5/8 + 7/8
7/8
7/8 + 7/8
7/8 + 7/8
7/8 + 7/8
7/8 + 7/8
7/8 + 7/8
7/8 + 1 1/8
Printed in U.S.A.
Form 38AP-5SI
The kit consists of a liquid line check valve and a bypass
check valve to prevent charge migration to compressor.
For all units with liquid lines of 100 ft (30.5 m) or more or
any 025-030 size dual circuit unit application where evapo-
rator is located higher than the condensing unit and liquid
lines exceed 55 feet (16.8 m), a long line check valve must
be installed to prevent compressor failure. The long line
check valve accessory must be mounted in the liquid line
as close as possible to the condensing unit.
The long line check valve accessory must be mounted in the
liquid line near the condensing unit. The valve is brazed into
the liquid line. Fitting adapters may be required to connect the
check valve to the liquid line. The valve may be mounted in
any orientation, horizontally or vertically. See Fig. 1 for dimen-
sions. Figure 2 shows the location of the check valves on a
rooftop installation. Figure 3 shows the location of the check
valves on a ground level installation.
ACCESSORY USAGE (QUANTITY) — PART NO. 38AP-900---
011
012
2
1
2
1
2
2
2
1
Pg 1
38APS025-065
38APD025-130
50/60 Hz
INSTALLATION
CAUTION
013
1
1
1
1
1
2
2
2
2
2
1
1
5-10
Replaces: New

Advertisement

loading

Summary of Contents for Carrier 38APD025-130

  • Page 1: Installation Instructions

    — 7/8 + 7/8 — 7/8 + 7/8 — 7/8 + 7/8 — 7/8 + 7/8 — 7/8 + 7/8 — — Form 38AP-5SI 38APS025-065 38APD025-130 50/60 Hz INSTALLATION CAUTION — — — — — — — — — —...
  • Page 2 20.000 (508) BYPASS CHECK VALVE 3.715 ENSURE FLOW ARROWS (94) ARE AS DEPICTED DIRECTION OF FLOW LIQUID LINE CHECK VALVE NOTE: Dimensions are in inches. Dimensions in () are in millimeters. Fig. 1 — Long Line Check Valve Accessory Dimensions (Part No. 38AP-900---011 Shown)
  • Page 3 Fig. 2 — Accessory Location — 38AP Unit Rooftop Installation NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes.
  • Page 4 Catalog No. 04-53380009-01 Printed in U.S.A. NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes. 3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific installation.