DMP Electronics SCS2 Installation Manual

DMP Electronics SCS2 Installation Manual

Multi-line digital receiver
Table of Contents

Advertisement

Quick Links

I N S T A L L A T I O N G U I D E
S C S 2
M u l t i - L i n e
D i g i t a l
R e c e i v e r
version 1.3
version 1.3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SCS2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for DMP Electronics SCS2

  • Page 1 I N S T A L L A T I O N G U I D E S C S 2 M u l t i - L i n e D i g i t a l R e c e i v e r version 1.3 version 1.3...
  • Page 2: Table Of Contents

    Modem II, Modem IIE, Modem IIIa² and BFSK Formats ....21 SCS2 Backplane Connection Diagram ..........3 SIA FSK ....................21 Connections for SCS2-200 Line Card Expansion ......... 3 Silent Knight FSK1, FSK2 ..............21 SCS2 UPS Connection Diagram ............4 Silent Knight FSK2 Protocol ..............
  • Page 3: Introduction

    15 individual line card modules (SCS2-200) and 30 telco • Battery backed up RAM on each SCS2-200 line card lines connected to a SCS2-300. The SCS2 can decode a variety module for programming and event buffers. of popular and widely used communication formats. Refer •...
  • Page 4: Virtual Receiver Architecture

    APPROVALS VIRTUAL RECEIVER ARCHITECTURE The most novel feature of the SCS2-200 is its ability to use Agency Listings the telephone company information delivered as DNIS (Dialed • UL 864 Control Units for Fire-Protective Signaling Number Information Service) or Caller ID. This allows the...
  • Page 5: Scs2 Backplane Connection Diagram

    Not used on Not used on 35Ah SCS2-300 SCS2-300 Transformer 16 V , 175 VA CONNECTIONS FOR SCS2-420 LINE CARD EXPANSION REFER TO SCS2-430 POWER CONNECTIONS REFER TO SCS2-430 CONNECTIONS MV3 MV2 SCS2 SUR-GARD SECURITY SYSTEMS LTD. NEXT MODULE...
  • Page 6: Scs2 Ups Connection Diagram

    SCS2 UPS CONNECTION DIAGRAM REFER TO SCS2-430 POWER CONNECTIONS REFER TO SCS2-430 CONNECTIONS SCS2 SCS2-430 POWER CONNECTIONS SCS2-430 CONNECTIONS Not used on Not used on SCS2-300 SCS2-300...
  • Page 7: Quick Start

    “OK”. will be displayed on the SCS2-300 LCD and the “ACK” light COM port properties windows should appear. The configuration will FLASH. Press the [ACK] button to silence the SCS2-300 should be : buzzer.
  • Page 8: Installation

    INSTALLATION MOUNTING THE RECEIVER PRINTER CONNECTIONS Install the SCS2 in a closed 19"/48cm rack or cabinet with Connect the parallel printer to the SCS2 printer output port a locking rear access door. Cover all unused spaces with using a standard parallel printer cable.
  • Page 9: Scs2-200 Digital Receiver Line Card

    The main functions of the line cards are to continuously monitor the telephone line, receive calls from digital dialers or control panels, and to report alarms to the SCS2-300. In addition, if a line card is unable to communicate with the SCS2-300, each line card is capable of functioning independently.
  • Page 10: Scs2-200 Operating Mode

    FLASH and the sounder will beep if the “Mute Buzzer” option is programmed as [00], [02] or [03]. When a SCS2-300 error is present, each alarm must be manually The cold booting procedure is covered in detail below.
  • Page 11 When a function is selected, press [ACK] and [SELECT] ACK:menu SEL:sel together to exit from the Menu mode. The SCS2-200 will automatically exit from the Menu mode if no keys are pressed With this message displayed, press the [SELECT] button; the for 30 seconds.
  • Page 12: Scs2-200 Cold Startup

    Stopping Data Reception Manually printer through the SCS2-300. Options [1D] and [1E] can be adjusted to allow the SCS2-200 To cancel communications between the SCS2-200 line card and the calling control panel, press the [CANCEL] button.
  • Page 13: Profiles

    The default setting is 0A, for 1 second. Each SCS2-200 can have a maximum of 64 profiles. To change the NOTE: If DNIS is used, this time will not start until DNIS options for a particular profile, utility software is provided. This is received.
  • Page 14: Default Dynamic Options

    Options [30] - [3F]: 3/1, 4/1 Format Event Codes The line is not seized if any of the conditions The SCS2-200 will use the last digit of data received in 3/ mentioned above occurs 1 and 4/1 formats to determine the computer event code.
  • Page 15 Option [74]: Equivalent Line Options [50] - [5F]: 4/3 Format Event Codes Selection The SCS2-200 will use the fifth digit of data received in 4/3 Equivalent line option is used when an incoming signal can be received on another receiver telephone line if the original and 4/2 extended formats to determine the message and event code.
  • Page 16 “36.” value greater than 20. Option [7B] may be used with any 3 digit account code formats supported by the SCS2. To disable the 3 digit account range [Default is 00] 2-Way Audio function, program Option [7B] as “00.” NOTES: Option [04] must have a value other than 00.
  • Page 17 Option [91]: Inter Handshake Duration second delay. The SCS2-200 line card will usually wait for signals from the Option 80 = 28 hex = 40 decimal * 100 ms = 4000 ms = 4 control panels for 4 seconds before sending the next handshake, second delay.
  • Page 18 1 extended format into 4/2 output for reporting to the computer and the printer. without checksum. Therefore, this option must be programmed to inform the SCS2-200 which of the 3 formats may be used. For example, with Option [96] enabled, the security control DMP DTMF 4/3 with checksum...
  • Page 19 Option [9D]: MODEM II RS-232 Option [A3]: D6500 computer output The SCS2-200 is able to decode the Modem II formats. The The SCS2-200 will emulate the Radionics D6500 RS-232 protocol handshake 0B needs to be programmed as one of the on pulse formats only (00 = disable, 01 = enable).
  • Page 20: Scs2-200 Communication Formats

    This format consists of 4-digit account codes, two digit format Computer: 1011ssssss123sAss32[14] Printer: L01-123-32-FIRE ALARM HH:MM:SS-DD/MM identifiers and 1- or 2-digit alarm codes. The SCS2-200 will • 4/2 FORMAT decode the signal as regular 4/1 or 4/2 format. Option [99] Computer: 1011ssssss1234sAss22[14] must be programmed as “01”...
  • Page 21: Ademco Super Fast (High Speed Format)

    P011ss12345sA00085555116NORTH OFFICE PRI15S. channel status digits, and 1 auxiliary channel. WEST BUILDING[DC4] NOTE: When option [9F] is programmed as “00,” the SCS2- 200 will convert the signal into 4/2 format. When option The above two automation signals are both DMP serial 1 [9F] is programmed as “01,”...
  • Page 22: Iti Format

    ITI FORMAT Commander 2000 The ITI format covers ITI panel models RF Commander, Sensor # Caretaker Plus, SX-V, SX-IVB, UltraGard 5000 (Pro 5000), 01-18 ALARM Commander III and Commander 2000 Simon. In order to ALARM receive the ITI format, the handshake 0E must be programmed. ALARM Upon a cold boot, the fifth handshake (option [86]) is ALARM...
  • Page 23: Modem Ii, Modem Iie, Modem Iiia² And Bfsk Formats

    50-59 Bypass 10-19 The standard SCS2-200 can receive Bell 103 modem frequencies. Trouble AC NOTE: The SCS2-200 can accept SIA formats with and with- 61-68 Trouble 1-8 out separators. The SCS2-200 version 1.3 software implements Trouble bat...
  • Page 24: Sescoa Super Speed

    SILENT KNIGHT FSK2 PROTOCOL Possible events are as follows: B600 Battery Trouble The SCS2-200 will provide two possible outputs to the computer, BE00 Battery Restore according to the value set under option A7. When the option C600 System Trouble AC is programmed as “00”...
  • Page 25: Scs2-200 Predefined Library Decoding And Event Codes Table

    SCS2-200 PREDEFINED LIBRARY DECODING AND EVENT CODES TABLE 3/1 - 4/1 Alarm Library 4/2 Extended & 4/3 Alarm Library For Alarm Corresponding Event Alarm 0xx(Axx) 0 PER TEST REPORT Message Code Code (Options 30-3F) Alarm 1xx A FIRE ALARM 0 (A) A...
  • Page 26: Scs2-300 - Central Processing Module

    Used to save changes and exit a mode; also used for other • Software version 2.4 (or higher) allows up to 30 line functions when indicated on the display screen. cards to be connected to a single SCS2-300. “AC” LIGHT Indicates that AC power is present.
  • Page 27: Scs2-300 Operating Mode

    05 COM1 Configuration Turn the “PROG EN” (Program Enable) switch ON. The Program 06 COM1 Format Enable switch is located on the left side of the SCS2-300 07 Acknowledge Wait Delay unit; use a small screwdriver to turn the switch ON by 08 Heartbeat Select turning it clockwise.
  • Page 28 Enter a number from 01 to 1E to indicate how many line Option [06] determines the communication format to be cards, from 1 to 30, are to be polled by the SCS2-300. When used on COM1. Press the [ACK] button when the 06: Com#1 the new number is entered, press the [Enter] button;...
  • Page 29 Option 12: UL Receiver Option [Enter] and [Backspace] buttons to move the cursor forward To have the SCS2 operate in compliance with UL Listed or backward when editing the heartbeat time. When Central Station requirements, press the [ACK] button when programming is complete, press the [Escape] button;...
  • Page 30 [Enter] button. When the [Enter] button is pressed, this message will be displayed: N represents the number of times the SCS2-300 tries to re- send the message to COM1; this value should be “1” during Are You Sure? normal communication.
  • Page 31 NOTE: This option will affect COM1 when COM1 is pro- grammed with communication format 4. Option 22: System Reset To reset the SCS2-300 program, press the [ACK] button when the “22: Force Reset” message is displayed; this message will be displayed:...
  • Page 32: Message Priorities

    MESSAGE PRIORITIES AC FAILURE When in Standby mode, the SCS2-300 will display warning If AC power is removed from the SCS2-300, this message will and other operational messages according to the following be displayed: priority: *Feb-23 07:30:45 UL Requirement Message <AC Power LOST!>...
  • Page 33 [D] SEND PRINTER MESSAGE TO THE PRINTER LCard#:FF ent:EXE With the SCS2-300 in the Standby mode, press the [D] key to Enter a hexadecimal number to view the following: send printer messages in the buffer to the printer. When the Enter...
  • Page 34 SCS2-300 Reset the data to COM1 and awaits an acknowledgment signal When a SCS2-300 event is sent to the computer that has the from the computer. If a NAK signal is received from the line card number in it, the SCS2-300 changes the value of computer, the SCS2-300 will make 4 attempts to send the the line card number to a letter.
  • Page 35: Scs2-300 Eprom Programming

    DATA BYTE PROTOCOL 6501-6502 3E80 Delay time x 0.25 ms to re-send The DMP SCS2 receiver uses a default configuration of 19200 message to COM1 if heartbeat is Baud, one start bit, seven data bits, one even parity bit, and not selected one stop bit structure to transmit and receive signals on the RS-232 port.
  • Page 36: Appendix A: Scs2-200 Communication Formats

    APPENDIX A: SCS2-200 COMMUNICATION FORMATS UL has verified compatibility with the following formats: NAME HANDSHAKE DATA BAUD FORMAT EXTENDED KISS OFF Ademco Slow 1400Hz 1900Hz 10bps 3/1,4/1(or 3/2),4/2 1400Hz Ademco Slow 1400Hz 1900Hz 10bps 4/2,4/1,3/1 1400Hz Silent Knight Fast 1400Hz...
  • Page 37: Appendix B: Ascii Character Chart

    APPENDIX B: ASCII CHARACTER CHART ASCII with library Corresponding ASCII on printer Character (Option 30) Space...
  • Page 38: Appendix C Decimal - Hex - Binary Conversion Chart

    APPENDIX C DECIMAL - HEX - BINARY CONVERSION CHART BINARY BINARY BINARY BINARY 0100 0000 0000 0000 1000 0000 1100 0000 0100 0001 0000 0001 1000 0001 1100 0001 0100 0010 0000 0010 1000 0010 1100 0010 0100 0011 0000 0011 1000 0011 1100 0011 0100 0100...
  • Page 39: Appendix D: Printer Words - Options [60] - [6F]

    APPENDIX D: PRINTER WORDS - OPTIONS [60] - [6F] The English Printer Library is provided and can be selected by programming the event codes to the corresponding word. Words available: 00 MEDICAL 46 FIRE SUPERVISORY 8C PROTECTION LOOP D2 SOUNDER/RELAY DISABLED 01 PENDANT TRANSMITTER 47 LOW WATER PRESSURE 8D PROTECTION LOOP OPEN...
  • Page 40: Appendix E: Default Static Options

    APPENDIX E: DEFAULT STATIC OPTIONS Option Option Option Option Option Description Description Description Description Description Default Default Default Default Default Option Option Option Option Option Description Description Description Description Description Default Default Default Default Default LINE # 0D, 0E CALLER SOURCE LINE # LENGTH LINE SEIZE EVENT DSC AUDIO...
  • Page 41: Appendix F: Default Dynamic Options

    APPENDIX F: DEFAULT DYNAMIC OPTIONS [30] - [AF] Line Card Configuration Command: LCard Comd Line Card Command(F7) Option Code Second Code Option Option Option Option Option Description Description Description Description Description Default Default Default Default Default Change Change Change Change Change ASCII (HEX) ASCII (HEX)
  • Page 42: Appendix G: Event Code Classifications

    APPENDIX G: EVENT CODE CLASSIFICATIONS The Event codes have been grouped according to the type of event, as described below. Medical Alarms - 100 303 RAM checksum bad 407 Remote arm/disarm 100 Medical 304 ROM checksum bad 408 Quick Arm 101 Pendant transmitter 305 System reset 409 Keyswitch O/C...
  • Page 43: Industry Canada Notice

    Industry Canada NOTICE Notice: The Industry Canada label identifies certified equipment. This certification d'exploitation et de sécurité des réseaux de télécommunications. Industrie Canada means that the equipment meets certain telecommunications network protective, n'assure toutefois pas que le matériel fonctionnera à la satisfaction de l'utilisateur. operational and safety requirements.
  • Page 44 Limited Warranty Digital Monitoring Products warrants that for a period of 36 months from the date of purchase, the product shall be free of defects in materials and workmanship under normal use and that in fulfillment of any breach of such warranty, Digital Monitoring Products shall, at its option, repair or replace the defective equipment upon return of the equipment to its repair depot.