Key Parts Checking - Klimairre KSIM018‐H210 Service Manual

Ksim series 3d dc inverter split wall-mounted type, units 18 – 24.000 btu/h; 230/208v, 60hz,1ph, r410a
Table of Contents

Advertisement

8.3 Key parts checking.

8.3.1. Compressor checking (Model: DA150S1C-20FZ)
Measure the resistance value of each winding by using the multi-meter.
8.3.2 Outdoor Fan Motor (Model: YDK53-6FB)
Measure the resistance value of each winding by using the multi-meter.
8.3.3 Outdoor Fan Motor (Model: YDK53-6NB)
Measure the resistance value of each winding by using the multi-meter.
8.3.4 Temperature Sensors.
Room temp.(T1) sensor,
Indoor coil temp.(T2) sensor,
Outdoor coil temp.(T3) sensor,
Outdoor ambient temp.(T4) sensor,
Compressor exhaust temp.(Te) sensor.
Measure the resistance value of each winding by using the multi-meter.
Some frequently-used R-T data for T1, T2, T3 and T4 sensor:
Temperature ( )
Resistance Value (KΩ)
Blue - Red
Blue - Black
Red - Blue
Black - Red
Red -Yellow
Black - Red
Red -Yellow
5
10
15
20
26.9
20.7
16.1
12.6
Position
Resistance Value
0.95Ω
(20 )
Position
Resistance Value
56Ω (20 )
76Ω (20 )
Position
Resistance Value
56.5Ω (20 )
117.5Ω (20 )
25
30
40
50
10
8
5.2
3.5
60
2.4
35