6. Installation details
6.1 Tightening Connection
Align the center of the pipes.
Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as
shown in Fig.
Outer diam.
Ф6.35mm
Ф9.52mm
Ф12.7mm
Ф16mm
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
6.3 Pipe length and the elevation
Capacity
Btu/h
Gas
18K
1/2'' (Ф12.7)
24K
5/8'' (Ф16.0)
Tightening torque(N.cm)
1/4"
1570(160kgf.cm)
3/8"
2940(300kgf.cm)
1/2"
4900(500kgf.cm)
5/8"
7360(750kgf.cm)
Unit
9K
2
mm
1.5
Pipe size
Liquid
1/4'' (Ф6.35)
3/8'' (Ф9.52)
Additional tightening torque(N.cm)
Grade
12K
18K
24K
1.5
2.5
2.5
Standard
Max.
length
Elevation
(m)
B (m)
5
8
5
10
1960(200kgf.cm)
3430(350kgf.cm)
5390(550kgf.cm)
7850(800kgf.cm)
Max.
Additional
Length
refrigerant
A (m)
(g/m)
15
20
20
40
12