Protection; Fan-Only Mode - Klimairre KSIM018‐H210 Service Manual

Ksim series 3d dc inverter split wall-mounted type, units 18 – 24.000 btu/h; 230/208v, 60hz,1ph, r410a
Table of Contents

Advertisement

FAN SPEED indication lamp
Displays the selected fan speed: AUTO (nothing) and three fan speed levels: LOW, MED and HIGH.
7.2.2 LED display control function.
Pressing "LED display" button on remote controller will turn off all displays on indoor unit, while pressing once
again, all displays will resume.

7.3 Protection

7.3.1 Three Minutes Delay at restart for compressor.
7.3.2 Temperature protection of compressor top.
7.3.3 If the temperature of compressor top is too high(higher than 115℃ and the Over-load Protector is cut, the units
stop. When the Over-load Protector restore and close(lower than 100℃), the compressor will restart( in this case
the compressor is restricted by Three Minutes Delay protection.
7.3.4 Temperature protection of compressor exhaust.
If the exhaust temp. of compressor is higher than 115℃ and lasts for 5 seconds, the compressor stops and does
not resume until the exhaust temp. is lower than 90℃.
7.3.5 Inverter module Protection, Inverter module Protection itself has a protection function against current, voltage and
temperature. If these protections happened, the corresponding code will display on indoor unit LED.
7.3.6 Sensor protection at open circuit and breaking disconnection
7.3.7 Fan Speed is out of control. When Indoor Fan Speed is too low (lower than 300RPM for 60 seconds), the unit
stops and LED displays failure information and can't return to normal operation automatically.
7.3.8 Cross Zero signal error warning. If there are 20 alternations of Cross Zero signals are incorrect, the unit stops and
LED displays failure information. After resuming, the motor rotates again. The spacing of Cross Zero signal is
6-13ms.
7.3.9 Indoor fan delayed open function
7.3.10 For all modes, when the units are turned on, the indoor fan can operate 10 seconds after the action of louver.
7.3.11 Compressor preheating function.
1)
Preheating permitting condition:
If T4(outdoor ambient temperature)<3℃ and the machine connects to power supply newly or if T4<3℃
and compressor has stopped for over 3 hours, the compressor heating cable will work.
2) Preheating mode:
A weak current flows through the coil of compressor from the wiring terminal of compressor, then the
compressor is heated without operation.
3) Preheating release condition:
If T4>5℃ or user turns on the machine and compressor runs, preheating function will stop.

7.4 Fan-Only Mode

7.4.1 Temperature setting function is disabled, and no setting temperature display.
7.4.2 In this mode, the action of louver is the same as in cooling mode.
7.4.3 The action of auto fan in fan-only mode is the same as auto fan in cooling mode with 24℃ setting temperature.
3.5
3.0
1.5
1.0
high
medium
low
21