Evacuation - Klimairre KSIM018‐H210 Service Manual

Ksim series 3d dc inverter split wall-mounted type, units 18 – 24.000 btu/h; 230/208v, 60hz,1ph, r410a
Table of Contents

Advertisement

6.8 Evacuation

Procedure:
1. Connect the vacuum pump to the charge set's centre hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle
does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
18