1. Precaution installation stand. 1.1 Safety Precaution It may cause injury, accident, or damage to the To prevent injury to the user or other people product. and property damage, the following instructions Be sure the installation area does not must be followed. deteriorate with age.
Page 5
It may cause corrosion on the product. Corrosion, arrives. particularly on the condenser and evaporator fins, There is risk of property damage, failure of product, could cause product malfunction or inefficient or electric shock. operation. Do not open the inlet grill of the product during operation.
Page 6
The chemical in batteries could cause burns or other your skin or clothes, wash it well with clean health hazards Do not use the remote of the batteries have leaked.
2. Function Indoor unit Operation by remote controller Sensing by room temperature Room temperature sensor. Pipe temperature sensor. Room temperature control Maintain the room temperature in accordance with the setting temperature. Anti-freezing control in cooling Prevent the water being frozen on evaporator by sensing the evaporator pipe temperature in cooling mode Ionizer Time Delay Safety control...
Page 8
Outdoor unit Power relay control The unit has 3 mins delay between continuously ON/OFF operations. Low noise air flow system Bird tail propeller fan makes the outdoor unit run more quietly. Hydrophilic aluminum fin The hydrophilic fin can improve the heating efficiency at operation mode. 4 way valve control It is only operated in the heating operation mode except defrosting operation.
6. Installation details 6.1 Tightening Connection Align the center of the pipes. Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as shown in Fig. Outer diam. Tightening torque(N.cm) Additional tightening torque(N.cm) Ф6.35mm 1/4”...
Caution: Capacity is base on standard length and maximum allowance length is base of reliability. Oil trap should be installed per 5-7 meters. 6.4 Air purging of the piping and indoor unit Required tools: Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector. Note: The air in the indoor unit and in the piping must be purged.
Page 17
tightened further, continue working from step (4). If the gas leaks do not stop when the connections are retightened, repair the location of the leak, discharge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.
6.5 Pumping down (Re-installation) Procedure 1. Confirm that both the 2-way and 3-way valves are set to the opened position. Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems. 2.
6.6 Re-air purging (Re-installation) Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the closed position. 2. Connect the charge set and a charging cylinder to the service port of the 3-way valve. Leave the valve on the charging cylinder closed. 3.
6.7 Balance refrigerant of the 2-way, 3-way valves Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the open position. 2. Connect the charge set to the 3-way valve’s service port. Leave the valve on the charge set closed. Connect the charge hose with the push pin to the service port.
6.8 Evacuation Procedure: 1. Connect the vacuum pump to the charge set’s centre hose. 2. Evacuation for approximately one hour. Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less]. 3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
6.9 Gas charging Procedure: 1. Connect the charge hose to the charging cylinder. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. 2. Purge the air from the charge hose. Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
7 Electronic function 7.1 Abbreviation T1: Indoor ambient temperature T2: Pipe temperature of indoor heat exchanger T3: Pipe temperature of outdoor heat exchanger T4: Outdoor ambient temperature 7.2 Display function 7.2.1 Icon explanation on indoor display board. OPERRATION indicator This indicator flashes after power is on and illuminates when the unit is in operation. AUTO indicator This indicator illuminates when the air conditioner is in AUTO operation.
FAN SPEED indication lamp Displays the selected fan speed: AUTO (nothing) and three fan speed levels: LOW, MED and HIGH. 7.2.2 LED display control function. Pressing “LED display” button on remote controller will turn off all displays on indoor unit, while pressing once again, all displays will resume.
7.5 Cooling Mode 7.5.1 After starting, the operation frequency of compressor submits to following rule. -0.5 -1.0 When the machine is running and ΔT(=room temp. – setting temp.) changes, the frequency of compressor will rise or descend a grade (7 minutes after starting). After start, if ΔT stays in a zone for 3 minutes, the frequency will change as follow: Zone A : Current frequency rise a grade till the maximum grade.
After running for 30 minutes the machine will turn back to previous setting mode. 7.5.6 Indoor fan operation rule. In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. Auto fan in cooling mode acts as follow: high medium...
Page 27
anti-cold-wind is disabled. 7.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential. Auto fan action in heating mode. medium high 7.7.3 After starting, the operation frequency of compressor submits to following rule: Remark: ΔTcon can be changed among 0, -2,- 4 , the default is 0 When the machine runs, if ΔTh stays in a zone for 3 minutes, action of frequency is as follow: Zone A: Elevate current frequency one grade, and not stop until the maximum grade.
Page 28
7.7.6 Defrosting mode Condition of defrosting. Condition 1: If T4>0℃, When the units are running, if the following two items are satisfied the units start defrosting: a) The units runs with T3<3℃ for 40 minutes and T3 keeps lower than -6℃ for more than 3 minutes.
Page 29
machine will turn into rating capacity test mode, the buzzer will make a “di” sound for 2 seconds continuously. Also, indoor fan will change to rating speed, the frequency of compressor will be fixed as rating value. Any condition of above is not satisfied, the machine can not be turned into rating capacity test mode.
7.8 Auto mode function 7.8.1 This mode can be chosen with remote controller and the setting temperature can be changed between 17~30℃. In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT(ΔT =T1-Ts). ΔT=T1-Ts Running mode ΔT>1℃...
7.12 Timer function 7.12.1 Timing range is 24 hours, and the minimum resolution is 15 minutes. 7.12.2 Timer on. After turning off, the machine will turn on automatically when reaching the setting time. 7.12.3 Timer off. After turning on, the machine will turn off automatically when reaching the setting time. 7.12.4 Timer on/off.
bright. After running for 13 minutes in low fan mode, the unit turns into low heating mode(anti-cold wind function is not valid), when the unit keeps low heating mode for 1 min or evaporator high temp protection occur, it stops and turns into low fan mode and keeps running for 2 minutes, then quits from Self-Clean function and turns off.
8. Troubleshooting Safety Because of there are capacitors in PCB and relative circuit in outdoor unit, even shut down the power supply, electricity power still are kept in capacitors, do not forget to discharge the electricity power in capacitor. Electrolytic Capacitors (HIGH VOLTAGE! CAUTION!) Bulb (25-40W)
8.1 Indoor Unit Error Display Display LED STATUS EEPROM parameter error Indoor / outdoor units communication protection Zero-crossing signal error Fan speed out of control Open or short circuit of outdoor temperature sensor Open or short circuit of room or evaporator temperature sensor IGBT over-strong current protection Over voltage or too low voltage protection Temperature protection of compressor top.
8.2 Diagnosis and Solution 8.2.1 E0(EEPROM parameter error) error diagnosis and solution Circuit or software error on indoor PCB Replace indoor PCB 8.2.2 E1(indoor / outdoor units communication protection) error diagnosis and solution Disconnect the power supply, after 1 minute, connect the power supply, turn on the unit with remote controller Does the unit work normally?
Page 36
8.2.4 E3(indoor fan speed out of control) diagnosis and solution Is the indoor fan motor Repair the connector and connector and connection reconnect good? Is voltage being applied to the fan motor? Indoor PCB is defective. (rang 90v-160v between Replace the indoor PCB. mid pin and N on CN1 Replace the indoor fan motor...
Page 37
8.2.8 P1(over voltage or too low voltage protection) diagnosis and solution. Be sure the power supply is Is the power supply good? normal when using the units Replace the outdoor e-box. 8.2.9 P2(temperature protection of compressor top) diagnosis and solution. Is the connection Does compressor Reconnect and retest.
8.3 Key parts checking. 8.3.1. Compressor checking (Model: DA150S1C-20FZ) Measure the resistance value of each winding by using the multi-meter. Position Resistance Value Blue - Red 0.95Ω Blue - Black (20 ) Red - Blue 8.3.2 Outdoor Fan Motor (Model: YDK53-6FB) Measure the resistance value of each winding by using the multi-meter.
Page 39
Some frequently-used R-T data for Te sensor: Temperature ( ) Resistance Value (KΩ) 141.6 56.1 36.6 13.8 KΩ...