bright. After running for 13 minutes in low fan mode, the unit turns into low heating mode(anti-cold wind function is not
valid), when the unit keeps low heating mode for 1 min or evaporator high temp protection occur, it stops and turns into
low fan mode and keeps running for 2 minutes, then quits from Self-Clean function and turns off.
3) When setting the Self-Clean function, the unit has been in Timer or Turbo function, the Timer or Turbo function will
be cancelled and then execute Self-Clean function.
4) When the unit is running Self-Clean function, all functions are not available except swing/air direction/clean air/LED
display, and only receiving "Self-Clean" code again or "turn off" code, the unit can quit from the function.
5) When the unit is running Self-Clean function, all protection functions are valid.

7.17 Follow me function

1)
Follow me function is chosen through wire jumper J1 in indoor PCB, it's available when the unit has detected that J1
is on after getting through the power.
2)
If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote controller, the
buzzer will emit a sound and this indicates the follow me function is initiated. But when the indoor PCB receives signal
which sent from remote controller every 3 minutes, the buzzer will not respond. When the unit is running with follow
me function, the PCB will control the unit according to the temperature from follow me signal, and the temperature
collection function of room temperature sensor will be shielded, but the error detective function of room temperature
sensor will be still valid.
3)
When the follow me function is available, the PCB will control the unit according to the room temperature from the
remote controller and the setting temperature, and the action of compressor is as following:
At cooling mode, if TA<TS, compressor is off; If TA≥TS, compressor is on.
At heating mode, if TA>TS, compressor is off; If TA≤TS, compressor is on.
4)
The PCB will take action to the mode change information from remote controller signal, but it will not affected by the
setting temperature.
5)
When the unit is running with follow me function, if the PCB doesn't receive any signal from remote controller for 7
minutes or pressing FOLLOW ME button again, the follow me function will be turned off automatically, and the
temperature collection function of room temperature sensor will be available, the PCB will control the unit according
to the room temperature detected from its own room temperature sensor and setting temperature.