Klimairre KSIM018‐H210 Service Manual page 27

Ksim series 3d dc inverter split wall-mounted type, units 18 – 24.000 btu/h; 230/208v, 60hz,1ph, r410a
Table of Contents

Advertisement

anti-cold-wind is disabled.
7.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential.
Auto fan action in heating mode.
7.7.3
After starting, the operation frequency of compressor submits to following rule:
When the machine runs, if ΔTh stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate current frequency one grade, and not stop until the maximum grade.
Zone B: Elevate or keep or descend current frequency.
Zone H: Compressor stops after running with F1 for 60 minutes or when ΔTh>6℃.
7.7.4 Outdoor unit current control in heating mode.
Remark:
KSIM024-H217
7.7.5 Indoor heat exchanger high temperature protection.
If T2>60℃, the compressor will stop and not resume until T2<48℃.
2.5
2.0
1.5
1.0
5.0
4.5
1.0
0.5
Remark: ΔTcon can be changed among 0, -2,- 4 , the default is 0
I3HEAT
I2HEAT
I1HEAT
I1HEAT
11 A
low
medium
high
H
B
A
comp. pause
freq. descends if curr. rises;
freq. remains if curr. descends
running normally
I2 HEAT
I3 HEAT
12A
13 A
24