10. Changing the setting of the functions
● Setting procedure
1. When the UPS is stopped with AC input supplied, while pressing the Stop Switch, press and hold the Start
Switch for at least 0.5 second.
2. The AC Input Lamp blinks and the Bypass mode Lamp or the Battery mode Lamp
goes on.
3. Under this condition, press and hold the Start Switch once for at least 0.5 second.
The Bypass mode or the Battery mode Lamp goes on alternately, which indicates
the change of the setting.
• When the Bypass mode Lamp goes on: Accepts both during Line mode and
during Battery mode.
In this case, the UPS stops when a continuous voltage signal of 10 seconds or
more is applied.
• When the Battery mode Lamp goes on: Accepts only during Battery mode.
In this case, the UPS stops when a continuous voltage signal of 0.01 second
(10 ms) or more is applied.
* Factory-shipped setting: Accepts only during Battery mode.
(The Battery mode Lamp goes on.)
4. When the desired setting is displayed, press and hold the Stop Switch for at least
2 seconds to complete the setting.
10-2 Functions that can be set/change from the
UPS monitoring software
1. Beeper ON/OFF setting
ON
: The beeper sounds when an alarm is necessary.
OFF
: The beeper is disabled.
* Factory-shipped setting: ON
2. Auto battery test ON/OFF
ON
: The battery test is automatically executed at intervals of 4 weeks.
If the test result shows that battery replacement is required, a replacement alarm occurs.
OFF
: The battery test executed at intervals of 4 weeks is automatically disabled.
Set to OFF, for example, when you want to disable a series of operation of the auto battery check
and Battery mode.
* Factory-shipped setting: ON
3. Auto restart ON/OFF
ON
: When the UPS is shut down and stopped by the UPS monitoring software or the contact signal at
the occurrence of a power failure and then the commercial power is restored, the UPS automati-
cally starts up and starts output.
OFF
: Even if the UPS is shut down and stopped by the UPS monitoring software or the contact signal
and then the commercial power is restored, the UPS does not start up. You can start it up only
manually by pressing the Start Switch.
* Factory-shipped setting: ON