Rinnai RCE-460PTR Service Manual page 35

Fan convector
Table of Contents

Advertisement

Normal OFF
The unit will go into Test Mode when the Test Switch is switched ON while the unit is operating.
The unit will go into each of the following modes during Test Mode : Low Pressure Mode, High
Pressure Mode, Decision Level Adjustment Mode, and Sensitive Selection Mode.
• Test Mode...................................................Disables the temperature controls and allows you to
• Low Pressure Mode...................................The modulating valve electric current value for low
• High Pressure Mode .................................The modulating valve electric current value for high
• Decision Level Adjustment Mode ...........The maximum flame failure detection level can be
• Sensitivity Selection Mode .......................The sensitivity can be changed over from 1 to 2, and
* To reset each mode, press the ON/OFF button to turn the unit OFF.
* If the Timer 1 button is not pressed during each mode, the updated setting will be cancelled and
the data will not be stored in memory.
* If the data is stored, it will return to test mode and the entered information will be displayed.
Convector 460/560PTR
Test
Button
Test Mode
change the level manually. (Cancels when the test
switch is turned on again, or when combustion ceases.)
The level can be raised/lowered with the temperature
control buttons " ∧ " and " ∨ ", however, if they are con-
tinuously pressed for at least 0.5 seconds, it will change
to level 12 or level 1.
combustion can be adjusted with the temperature " ∧ "
and " ∨ " buttons. After adjusting, the data will be stored
when Timer 1 is switched ON.
combustion can be adjusted, with the temperature " ∧ "
and " ∨ " buttons. After adjusting, the data will be stored
when Timer 1 is switched ON.
adjusted with the temperature " ∨ " button, and the mini-
mum with the temperature " ∧ " button. They can be set
in the following order: 12mV, 14mV, 16mV, 18mV.
After adjusting, the data will be stored when Timer 1 is
switched ON.
vice versa, with the temperature " ∨ " button. After
adjusting, the data will be stored when Timer 1 is
switched ON. It is factory set at sensitivity level 2.
Low Pressure Mode
Sensitivity
Selection Mode
- 30 -
High Pressure Mode
Decision Level
Adjustment Mode
©Rinnai