Zone Sensors - Trane Voyager WS 150-24 Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners – heat pump 121/2 – 20 ton, 60/50 hz
Table of Contents

Advertisement

General Information
stream or return air stream, the air velocity entering the
smoke detector unit must be between 500 and 4000 feet
per minute. Equipment covered in this manual will
develop an airflow velocity that falls within these limits
over the entire airflow range specified in the evaporator
fan performance tables.

Zone Sensors

Note: Zone sensor required for units configured for
Single Zone VAV indoor fan system control to
enable Single Zone VAV functionality.
Zone Sensor Module (ZSM)
(BAYSENS107*)
This electronic sensor features three system switch
settings (Heat, Cool, and Off) and two fan settings (On and
Auto). It is a manual changeover control with single
setpoint. (Cooling Setpoint Only)
Zone Sensor (BAYSENS109*)
This electronic sensor features four system switch settings
(Heat, Cool, Auto, and Off) and two fan settings (On and
Auto) with four system status LED's. It is a manual or auto
changeover control with dual setpoint capability. It can be
used with a remote zone temperature sensor
BAYSENS075*.
Programmable Zone Sensor
(BAYSENS119*)
Programmable Night Setback: Auto or manual changeover
with seven-day programming. Keyboard selection of Heat,
Cool, Fan, Auto, or On. All programmable sensors have
System On, Heat, Cool, Service LED/indicators as
standard. Night Setback Sensors have one (1) Occupied,
one (1) Un-occupied, and one (1) Override program per
day.
Remote Zone Sensor (BAYSENS073*)
This electronic sensor features remote zone sensing and
timed override with override cancellation. It is used with a
Trane Integrated Comfort™ building management
system.
Remote Zone Sensor (BAYSENS074*)
This electronic sensor features single setpoint capability
and timed override with override cancellation. It is used
with a Trane Integrated Comfort™ building management
system.
Remote Zone Sensor (BAYSENS016*)
This bullet type temperature sensor can be used for;
outside air (ambient) sensing, return air temperature
sensing, supply air temperature sensing, remote
temperature sensing (uncovered). Wiring procedures vary
according to the particular application and equipment
10
involved. Refer to the unit's wiring diagrams for proper
connections.
Remote Zone Sensor (BAYSENS075*)
This electronic sensor can be used with BAYSENS106*,
108*, 110*, 109* Remote Panels. When this sensor is wired
to a BAYSENS109* Remote Panel, wiring must be 18 AWG
Shielded Twisted Pair (Belden 8760 or equivalent). Refer to
the specific Remote Panel for wiring details.
Wireless Zone Sensor (BAYSENS050)
This electronic sensor features five system settings (Auto,
Off, Cool, Heat, and Emergency Heat) and with On and
Auto fan settings. It is a manual or auto changeover control
with dual setpoint capability. Other features include a
timed override function, lockable system settings, and
Fahrenheit or Celsius temperature display. Included with
the wireless zone sensor will be a receiver that is to be
mounted inside the unit, a mounting bracket, and a wire
harness.
Thermostat (BAYSTAT150)
This thermostat is a multi-stage 3 heat/2 cool, auto-
changeover digital display thermostat. It is a
programmable thermostat, and a 7-day programmable
stat with night setback shall be available. In addition, it is
wall mounted.
Thermostat (BAYSTAT151)
This thermostat is a single-stage 1 heat/1 cool, auto-
changeover digital display thermostat. It is a non-
programmable, wall-mounted thermostat.
Thermostat (BAYSTAT155)
This thermostat is a multi-stage 3 heat/2 cool, auto
changeover digital display thermostat. It is a non-
programmable, wall-mounted thermostat, and it can be
used for Economizer Operation.
Human Interface - 5 Inch Color
Touchscreen (Optional)
The 5 inch Color Touchscreen Human Interface provides an
intuitive user interface to the rooftop unit that speeds up
unit commissioning, shortens unit troubleshooting times,
and enhances preventative maintenance measures. The
human interface includes several features including:
Data trending capabilities by means of time series
graphs
Historical alarm messages
Real-time sensor measurements
On board system setpoints
USB port that enables the downloading of component
runtime information as well as trended historical
sensor data
Customized reports
RT-SVX33E-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents