Manifold & Incoming Pressure Check Procedures - kozy heat MINNETONKA 55345 Installation And Operating Manual

Direct vent gas fireplace
Hide thumbs Also See for MINNETONKA 55345:
Table of Contents

Advertisement

MODEL #55345-RF: PRESSURE TEST - MANIFOLD & INLET PRESSURE
IMPORTANT NOTICE: A pressure check tap for both the manifold (outgoing) and inlet (incoming) pressure has been
incorporated into the valve by HONEYWELL Controls. The left pressure tap is the manifold pressure and the right pressure
tap measures the incoming pressure. Follow the instructions below for proper pressure testing procedures.
NOTE: Both the inlet and outlet pressure taps have a captive screw.
1. Be sure the gas control knob is in the PILOT position.
2. Light the pilot.
3. Loosen, but do not remove the outlet tap captive screw.
4. Attach a plastic tube with a 1/4" shell ID and connect the manometer.
5. Turn the gas control knob to the ON position.
6. Check the outlet tap pressure.
7. Turn the gas control knob to the OFF position.
8. Shut off the gas supply at the manual valve in the gas piping to the appliance or, for LP, at the tank.
9. Loosen, but do not remove the inlet tap captive screw.
10. Attach a plastic tube with a 1/4" shell ID and connect the manometer.
11. Turn on the gas supply at the manual valve.
12. Check the inlet tap pressure.
13. Turn the gas control knob to the OFF position.
14. Repeat the Gas Leak Test at the pressure tap with the main burner operating.
15. Always tighten the screws in the pressure taps after disconnecting the plastic tubes.
Figure 24
GAS LEAK TEST:
1. Paint the pipe connection upstream of the gas valve with a rich soap and water solution. Bubbles indicate a
gas leak.
2. If a leak is detected, tighten the pipe connections.
3. Light the main burner.
4. With the main burner in operation, paint the pipe joints (including adaptors) and valve inlet and outlet with a
rich soap and water solution.
5. If another leak is detected, tighten the adapter screws, joint, and pipe connections.
6. Replace the part if the leak cannot be stopped.
Page 30