Ipm Module Protection; Trouble Shooting - Pioneer YN018GMFI16M2D Service Manual

Yn-m series multi split system multi circuit outdoor units (2, 3 and 4 zones) service manual
Hide thumbs Also See for YN018GMFI16M2D:
Table of Contents

Advertisement

9.4.1.6 IPM module or IGBT over-strong current protection diagnosis and solution.
Malfunction decision
conditions
Supposed causes

Trouble shooting:

IPM module protection
Check whether the voltage range 
of P‐N on IPM module is normal? 
DC277‐356V for 18‐27KBtu/h; 
DC277‐410V for 36KBtu/h
Yes
Check whether the connecting 
line between main board and 
the IPM module is connected 
tightly
Yes
Check whether the connecting 
line of the compressor is 
connected correctly or tightly
Yes
Replace the IPM module, 
check whether the system can 
work normally?
No
Check if the outdoor fan 
runs properly or the outdoor 
unit ventilation is good.
No
Replace the main board; check 
whether the system can work 
normally?
No
Replace the compressor, check 
Yes
whether the system can work 
normally?
When the voltage signal that IPM send to compressor drive
chip is abnormal, the display LED will show "P6" and AC will
turn off.
● Wiring mistake
● IPM malfunction
● Outdoor fan ass'y faulty
● Compressor malfunction
● Outdoor PCB faulty
Check whether the input 
No
power supply is correct? 
Connect it tightly, 
No
check ok or not?
connected correctly and 
No
Connect it well, check 
No
ok or not?
Check whether the lines 
No
For AC fan models,  please refer 
to 9.4 Trouble Criterion Of Main 
Parts, check whether the 
Yes
resistance of the fan motor is 
normal. If not, replace the fan 
Yes
motor. 
efer to 
For DC fan models, r
the solution of fan speed has 
been out of control malfunction 
. Find out the cause and have it 
solved.
Yes
Yes
Trouble is solved
Regulate it to correct, then 
No
check whether the system 
208‐230V, 1N, 60Hz
can work normally?
No
Yes
Check whether the 
Connect it correctly 
power supply line is 
No
and tightly, check ok 
tightly
Yes
No
Connect it tightly, 
in E‐part box are 
No
check ok or not?
connected tightly
Yes
No
Check whether the bridge rectifiers are 
normal? Use the multimeter to measure 
the resistance between each two 
terminals, check whether there is the 
condition that value of resistance is 0
Yes
Replace the bridge rectifiers
Check  whether  the  connecting  line  of 
every  reactor  is  normal?  If  the  line  is 
broken, the resistance of the two ports is 
∞(models  except  for  M4OC‐36HRFN1‐
M&
M4OC‐36HRDN1‐M);Check 
whether  the  PFC  module  broken  (for 
M4OC‐36HRFN1‐M&
M4OC‐36HRDN1‐
M)
Replace the connecting line or 
reactor or replace the PFC 
module(for M4OC‐36HRFN1‐M)
or not?
No
No