Inverter Module (Ipm) Malfunction Diagnosis And Solution - Pioneer YN020GMFI22M2D Service Manual

Multi split system outdoor units/two, three, four and five zones
Hide thumbs Also See for YN020GMFI22M2D:
Table of Contents

Advertisement

8.4.1.6 Inverter module (IPM) malfunction diagnosis and solution.

Malfunction decision
conditions
Supposed causes
Trouble shooting:
IPM module protection
Check whether the voltage range 
of P‐N on IPM module is normal? 
DC277‐356V for 18‐27KBtu/h; 
DC277‐410V for 36K‐48KBtu/h
Yes
Check whether the connecting 
line between main board and 
the IPM module is connected 
tightly
Yes
Check whether the connecting 
line of the compressor is 
connected correctly or tightly
Yes
Replace the IPM module, 
check whether the system can 
work normally?
No
Check if the outdoor fan 
runs properly or the outdoor 
unit ventilation is good.
No
Replace the main board; check 
whether the system can work 
normally?
No
Replace the compressor, check 
whether the system can work 
normally?
Yes
When the voltage signal that IPM send to compressor drive
chip is abnormal, the display LED will show "P6" and AC will
turn off.
● Wiring mistake
● IPM malfunction
● Outdoor fan ass'y faulty
● Compressor malfunction
● Outdoor PCB faulty
No
Connect it tightly, 
No
check ok or not?
No
Connect it well, check 
No
ok or not?
No
For AC fan models,  please refer 
to 9.4 Trouble Criterion Of Main 
Parts, check whether the 
resistance of the fan motor is 
normal. If not, replace the fan 
Yes
motor. 
efer to 
For DC fan models, r
the solution of fan speed has 
been out of control malfunction 
. Find out the cause and have it 
solved.
Yes
Yes
Trouble is solved
Check whether the input 
Regulate it to correct, then 
power supply is correct? 
No
check whether the system 
208‐230V, 1N, 60Hz
can work normally?
No
Yes
Check whether the 
power supply line is 
No
connected correctly and 
tightly
Yes
No
Check whether the lines 
Connect it tightly, 
in E‐part box are 
No
check ok or not?
connected tightly
Yes
No
Check whether the bridge rectifiers are 
normal? Use the multimeter to measure 
the resistance between each two 
terminals, check whether there is the 
condition that value of resistance is 0
Yes
Yes
Check  whether  the  connecting  line  of 
every  reactor  is  normal?  If  the  line  is 
broken, the resistance of the two ports is 
∞;Check  whether  the  PFC  module 
broken .
reactor or replace the PFC module
Connect it correctly 
and tightly, check ok 
or not?
No
Replace the bridge rectifiers
No
Replace the connecting line or 