Error Code - Pioneer YN018GMFI16M2D Service Manual

Yn-m series multi split system multi circuit outdoor units (2, 3 and 4 zones) service manual
Hide thumbs Also See for YN018GMFI16M2D:
Table of Contents

Advertisement

9.4.2.8 P0(Temperature protection of compressor top) error diagnosis and solution. (Only for
YN027GMFI16M3D)

Error Code

Malfunction decision
conditions
Supposed causes
Trouble shooting:
Temperature protection of
compressor top
Whether compressor
operates?
Yes
Whether refrigerant
circulation volume is
normal?
No
Charge refrigerant
Whether abnormality is the
same after gas charging?
No
Check refrigerant system
(such as clogging of capillary
etc.)
P0
If the sampling voltage is not 5V, the LED will display the failure.
● Wiring mistake
● Over load protector faulty
● System block
● Outdoor PCB faulty
Whether the connection is
No
good?
Yes
Whether protector is normal? If
protector is normal,resistance = 0
Yes
Replace the outdoor main PCB
No
Reconnect and retest.
No
Replace the protector.