Guide Specifications; Air Conditioner - Carrier 38CKS Product Data

(60 hz) 10 seer air conditioner export models sizes 018 thru 060
Table of Contents

Advertisement

Guide specifications
GENERAL
System Description
Outdoor-mounted, air-cooled, split-system air conditioner
unit suitable for ground or rooftop installation. Unit consists
of a hermetic compressor, an air-cooled coil, propeller-type
condenser fan, and a control box. Unit will discharge supply
air upward as shown on contract drawings. Unit will be used
in a refrigeration circuit to match up to a packaged fan coil
or coil unit.
Quality Assurance
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards
and will carry the UL label of approval. Unit will have c-UL
approval.
The condenser coil will be capable of withstanding the
following test method standards: Salt Spray test, ASTM
B117 1,000 hrs, and the Prohesion Test ASTM G85-A5
1,000 hrs.
Air-cooled condenser coils will be leak tested at 150 psig
(1034 KPa) and pressure tested at 300 psig (2068 KPa).
Unit constructed in ISO 9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored
and handled per unit manufacturer's recommendations.
PRODUCTS
Equipment
Factory-assembled, single-piece, air-cooled air conditioner
unit. Contained within the unit enclosure is all factory
wiring, piping, controls, compressor, refrigerant charge
(R22), and special features required prior to field start-up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
Fans
Condenser fan will be direct-drive propeller type,
discharging air upward.
Condenser fan motors will be totally enclosed, 1-phase
type with class B insulation and permanently lubricated
bearings.
Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book
1
2
4
Page 24
Tab
3a 1a 2a
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with PVC-coated
steel wire safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins with a resin-
based epoxy phenolic thermoset coating, factory applied by
pre-coating and baking. The fins are mechanically bonded to
copper tubes which are then cleaned, dehydrated, and sealed.
Refrigeration Components
Refrigeration circuit components will include liquid line
shutoff valve with sweat connections, suction line shutoff
valves with sweat connections, system charge of R22
refrigerant, and compressor oil.
Operating Characteristics
The capacity of the unit will meet or exceed _____ Btuh at
a suction temperature of _____ °F (°C). The power
consumption at full load will not exceed _____ kW.
Combination of the unit and the evaporator or fan coil unit
will have a total net cooling capacity of _____ Btuh (kW) or
greater at conditions of _____ CFM entering air temperature
at the evaporator at _____ °F (°C) wet bulb and _____ °F
(°C) dry bulb, and air entering the unit at _____ °F (°C).
The system will have a SEER of _____ Btuh/watt or greater
at DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of satisfactory
operation within voltage limits of _____ v
to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
Indianapolis, IN 46231
Catalog No. 38CKS-5PD
Air-Cooled, Split-System
1-1/2 to 5 Tons Nominal
9-05
Printed in U.S.A.
PC 101