Split system air conditioner

Advertisement

38CKC
Split System Air Conditioner
For Use With R---22 Refrigerant
Export Model
1---1/2 To 5 Nominal Tons (Sizes 18---60)

SAFETY CONSIDERATIONS

CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper unit
operation.
This unit does not contain refrigerant and has a nitrogen
holding charge. Prior to operation, the nitrogen holding charge
must be evacuated and the unit charged with R22 refrigerant
per these instructions.
Use only R22 refrigerant when servicing this unit.
DO NOT use R410A refrigerant in this system.
This unit is factory shipped with the correct amount of
compressor oil. Additional oil does not need to be added to
this unit.
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory- -authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety- -alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety- -alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.

Installation Instructions

!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
handling parts.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.

INSTALLATION RECOMMENDATIONS

NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, and so forth,
where unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
to capacity of unit.
3. Run refrigerant tubes as directly as possible by avoiding un-
necessary turns and bends.
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal open-
ing with RTV or other pliable silicon- -based caulk. (See Fig.
! !
1.)
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap that comes in direct contact with tubing.
(See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
CAUTION
WARNING

Advertisement

loading

Summary of Contents for Carrier 38CKC

  • Page 1: Installation Instructions

    38CKC Split System Air Conditioner For Use With R---22 Refrigerant Export Model 1---1/2 To 5 Nominal Tons (Sizes 18---60) Installation Instructions SAFETY CONSIDERATIONS CAUTION CAUTION CUT HAZARD Failure to follow this caution may result in personal injury. UNIT OPERATION HAZARD Sheet metal parts may have sharp edges or burrs.
  • Page 2: Clearance Requirements

    CLEARANCE REQUIREMENTS CAUTION When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm) UNIT OPERATION HAZARD clearance to service end of unit and 48 in. (1219.2 mm) (above unit. For proper airflow, a 6- -in. (152.4 mm) clearance on 1 side of Failure to follow this caution may result in improper product unit and 12- -in.
  • Page 3 Condenser, line set, and indoor coil should be evacuated using the CAUTION recommended deep vacuum method of 500 microns. If deep vacuum equipment is not available, the alternate triple evacuation method may be used by following the specified procedure. UNIT OPERATION HAZARD If vacuum must be interrupted during the evacuation procedure, Failure to follow this caution may result in improper unit always break vacuum with dry nitrogen.
  • Page 4 DISCONNECT WARNING PER N.E.C. AND/OR LOCAL CODES CONTACTOR PERSONAL INJURY and ENVIRONMENTAL HAZARD Failure to relieve system pressure could result in personal FIELD POWER injury and/or death. WIRING 1.Relieve pressure and recover all refrigerant before BLUE 3 PHASE ONLY servicing existing equipment, and before final unit disposal.
  • Page 5: Check Charge

    by weight based on line length and allow the indoor temperature to CAUTION drop to 80_F (26.67_C) before attempting to check system charge by subcooling method as described above. If the indoor temperature is below 70_F (21.11_C), or the outdoor UNIT DAMAGE HAZARD temperature is not in the favorable range, adjust charge for line set Failure to follow this caution may result in unit damage.
  • Page 6 Catalog No: 38CKC ---EDRYSI Copyright 2011 CAC / BDP . S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 12/11 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.