Below Grade Installations - Majestic DV6000 Installation And Operating Instructions Manual

Direct vent gas fireplace
Table of Contents

Advertisement

DV6000 Gas Fireplace

Below Grade InstallatIons

When it is not possible to meet the required vent terminal clearances of 1" above grade level, a
snorkel kit is recommended. It allows installation depth down to 7" (178 mm) below grade level.
The 7" (178 mm) is measured from the center of the horizontal vent pipe as it penetrates through
the wall.
ensure that sidewall venting clearances are observed. If venting system is installed below
ground, we recommend a window well with adequate and proper drainage to be installed
around the termination area.
If installing a snorkel, a minimum 4" vertical rise is necessary. The maximum horizontal run with
the 4" vertical pipe is 36". This measurement is taken from the collar of the fireplace (or transition
elbow) to the face of the exterior wall. Refer to the Sidewall Venting Graph for extended horizontal
run if the vertical exceeds 4".
1. Establish vent hole through the wall. Refer to Page 20, Figure 16
. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install
window well (not supplied). Refill hole with 1" of coarse gravel leaving a clearance of approxi-
mately 4" below snorkel. Figure 27
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe
coming through the wall.
5. Slide the snorkel into the vent pipes and secure to the
wall.
6. Level the soil so as to maintain a 4" clearance below
snorkel. Figure 27
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the
snorkel. Fasten brackets to wall first, then secure to snorkel with self drilling #8 x 1/" sheet metal
screws. It will be necessary to extend vent pipes out as far as the protruding wall face. Figure 28
Firestop
4"
Minimum
Figure 27 -
FP1965
Below Grade Installation
below grade install
4
Screws
Minimum
4" Clearance
Ground
Gravel
Drain
Foundation Wall
FP1965
• do not back fill around snorkel.
• a clearance of at least 4" must be maintained
between the snorkel and the soil.
Foundation
Recess
Window Well
Watertight Seal
Around Pipe
Figure 28 -
Snorkel Installation, Recessed Foundation
FP1966
snorkel
vent InstallatIon
Snorkel
Wall Screws
Sheet Metal
Screws
FP1966
53D0419