vent InstallatIon
vertIcal throuGh-the-rooF applIcatIons
This Gas Fireplace has been approved for,
Vertical installations up to 40' (1 m) in height. Up to a 10' (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90° elbows. Figure 29
40' Maximum Height
8' Minimum Height
Up to two 45° elbows may be used within the
horizontal run. For each 45° elbow used on
the horizontal plane, the maximum horizontal
length must be reduced by 18" (450 mm).
example: Maximum horizontal length
No elbows = 10' (3 m)
1 x 45° elbows = 8.5' (.6 m)
 x 45° elbows = 7' (.1 m)
A minimum of an 8' (.5 m) vertical rise is
required.
Two sets of 45° elbows offsets may be used within
the vertical sections. From 0 to a maximum of 8'
(.5 m) of vent pipe can be used between elbows.
Figure 30
The maximum angular variation allowed in the
system is 70°. Figure 30
The minimum height of the vent above the high-
est point of penetration through the roof is ' (610
mm).
53D0419
10'
Maximum
Support Straps
Every 3'
Figure 29 -
Support Straps for Horizontal Runs
FP2308
support straps
40' Maximum Height
8' Minimum Height
1
2
3
4
Example:
Elbow 1
Elbow 
Elbow 3
Elbow 4
Total Angular Variation
Figure 30 -
Maximum Elbow Usage
DV6000 Gas Fireplace
10'
Maximum
Support Straps
Every 3'
FP308
1
2
=
90°
3
=
45°
=
45°
4
=
90°
=
70°
FP2309
max elbow use A
FP309
5