Suction Accumulator Operation Quietqube® Remote Condensing Unit - Manitowoc Indigo Series Technician's Handbook

Indigo series ice machine
Hide thumbs Also See for Indigo Series:
Table of Contents

Advertisement

SUCTION ACCUMULATOR OPERATION
QUIETQUBE® REMOTE CONDENSING UNIT
Liquid refrigerant collects in the suction accumulator
during the harvest cycle and is removed during the
freeze cycle. The liquid refrigerant is returned to the
compressor through a screen and orifice in the suction
accumulator J tube. Passing the liquid through the
orifice causes a pressure drop; the liquid flashes to a
vapor and creates a refrigeration affect. It is normal to
see frost on the accumulator, suction line and
compressor suction port in the freeze cycle. The
suction accumulator empties within the first 5 minutes
of the freeze cycle. When the refrigeration affect ends
(liquid refrigerant has been removed), the suction line
between the accumulator and compressor will
increase in temperature. The suction line temperature
increases 20 plus degrees within 2 minutes after the
liquid has been removed.
1
2
Minute
Minutes
The time needed to remove the liquid refrigerant will
vary with the ambient temperature and the length of
the harvest cycle. Higher ambient temperatures =
shorter harvest cycles, faster removal of liquid
refrigerant from the accumulator and greater suction
line temperature increases.
Part Number Preliminary 6/11
Temperature Increases
20+ºF (18+ºC)
3
4
Minutes
Minutes
6
Minutes
5
Minutes
8
7
Minutes
Minutes
275