Advertisement

12
Stove Installation

Chimney Termination Requirements

Must have an approved cap (to prevent water from entering)
Must not be located where it will become plugged by snow or other material
Must terminate at least 3' above the roof and at least 2' above any portion of the roof within 10' (see
Figure 5).
Min. 3' (914mm)
Min. 3' (914mm)

Outside Air Requirements

Required for mobile homes & in certain localities (check with building officials).
Must not be drawn from an enclosed space (garage, unventilated crawl space). May be drawn from
ventilated crawl space (a) or exterior of home (d). Must have suitable rodent/debris screen and rain
protection (hood).
Requires the optional outside air kit (sku 99200139 – see (c) and (e) below), air boot (for legs), or
pedestal (b).
Air duct maximum length is 15' (4.57M) with a minimum cross section of 16 square inches
(10404mm) or 6' (1.82M) with a minimum cross section of 7 square inches (4489mm).
a
© Travis Industries
c
(for qualified installers only)
Min. 2' (610mm)
10' (3.04M)
Min. 2' (610mm)
10' (3.04M)
b
e
d
100-01334
Figure 5
d
Figure 6
4131122