Specifications - Samlexpower SEC-40BRM-220 Installation & Operating Manual

N+1 dc power system with battery backup / charging function
Table of Contents

Advertisement

SPECIFICATIONS

NO. OF MODULES
INPUT VOLTAGE RANGE
INPUT CURRENT
OUTPUT VOLTAGE (At terminals L+ & L- , See page 7)
NOMINAL, VDC
NO LOAD, VDC
FULL LOAD, VDC
OUTPUT REGULATION
(At module output S5, S6—Fig. 1)
OUTPUT CURRENT
CONTINUOUS
SURGE
OUTPUT CURRENT LIMIT
OUTPUT RIPPLE, PEAK TO PEAK
OUTPUT NOISE, PEAK TO PEAK
COOLING
OPERATING TEMPERATURE
PROTECTIONS
SHORT CIRCUIT
CURRENT LIMIT
FAN FAILURE
INPUT SURGE SUPRESSION YES
FUSE / BREAKER
DIMENSIONS(19" Rack Mount, 2U height) 19" X 15.9" X 3.6"
POWER CORD
POWER CORD PLUG
WEIGHT, LBS
NOTE: SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
SEC-40BRM SEC-60BRM
SEC-80BRM
2
3
210 TO 250 V AC, 50/60 HZ
4A
6A
13.8 V
14 V
13.65 V
13.55 V
1%
40A
60A
46A
69A
48A
72A
150mV
1V
0.9V
FORCED AIR, 2 FANS
0 TO 40 C
YES
YES
LED AND BUZZER
● MODULE FUSE – 250 V, 4 A
● UNIT HAS A BREAKER
3 CONDUCTOR, 1.0 mm
European "Schuko", 250V, 16A
20.5
22
16.
SEC-100BRM
4
5
8A
10A
13.45 V
13.35 V
80A
100 A
92A
115A
96A
120A
0.8V
0.7V
2
23.5
25

Advertisement

Table of Contents
loading

Table of Contents