Trouble Shooting - Samlexpower SEC-40BRM-220 Installation & Operating Manual

N+1 dc power system with battery backup / charging function
Table of Contents

Advertisement

REMOVING A DEFECTIVE MODULE
1. Remove the top cover plate by unscrewing the 10 screws.
2. Locate the defective module. Remove the 6 screws from S1 to S6.
3.
Remove the input power supply wires from terminals "L" and "N". Insulate the
wire terminals with insulating tape
4. Remove connectors from terminals "LED 1 & LED 2" .
5.
Remove the "SHARE BUS" wire female socket connector from the terminal
"JUMP1". If the defective module is not being replaced immediately and if the
unit is required to be operated without this defective module.
IT IS MANDATORY TO SHORT THE TWO FEMALE SOCKETS ON
THIS UNUSED FEMALE CONNECTOR WITH A SHORTING LINK.
(SEE FIG. 3 ) THIS WILL ENSURE THAT THERE IS NO BREAK IN
THE "SHARE BUS" DAISY CHAIN AND THAT ALL THE "JUMP1"
TERMINALS ARE INTERCONNECTED.
6.
The module can now be removed

TROUBLE SHOOTING

POWER ON/OFF SWITCH DOES NOT LIGHT WHEN SWITCHED ON
Check that power is available in the AC outlet
·
Check that the power cord plug is properly plugged in
·
BREAKER TRIPS
The breaker has tripped due to abnormal condition. Call technical support
·
"FAN FAILURE" LED LIGHTS UP AND BUZZER IS SOUNDED
One or both of the fans have stopped
·
Forced cooling has failed due to defect in the cooling fan(s). Switch off the
unit immediately. Fan(s) needs to be replaced.
DO NOT USE THE UNIT TILL THE DEFECT IS RECTIFIED. IT IS PRO-
HIBITED TO USE THE UNIT WITHOUT FORCED COOLING. Call techni-
cal support.
If both the fans are running, the small fan status monitoring PCB may be
·
defective. Call technical support.
.