Mitsubishi Electric MXZ-2C30VA Service Manual page 75

Split-type air conditioners outdoor unit
Hide thumbs Also See for MXZ-2C30VA:
Table of Contents

Advertisement

MXZ-6C
Upper or
left lamp of
OPERATION
Abnormal point
INDICATOR
(Failure mode/protection)
lamp (Indoor
unit)
OFF
None (Normal)
2-time fl ash
Outdoor power system
3-time fl ash
Discharge temperature thermis-
tor
Defrost thermistor
Ambient temperature thermistor
Fin temperature thermistor
P.C. board temperature thermis-
tor
Outdoor heat exchanger tem-
perature thermistor
4-time fl ash
Overcurrent
Out-of-step protection
5-time fl ash
Discharge temperature
6-time fl ash
High pressure
7-time fl ash
Fin temperature
P.C. board temperature
8-time fl ash
Outdoor fan motor
9-time fl ash
Nonvolatile memory data
10-time fl ash
Discharge temperature
LED indication
(Outdoor P.C. board)
LED 1
LED 2
Lighting
Lighting
Lighting
Lighting
Overcurrent protection cut-out operates
3 consecutive times, bus-bar voltage
protection cut-out operates 3 consecu-
tive times, or primary current protection
cut-out operates 3 consecutive times
within 1minute after the compressor
gets started.
Lighting
Once
Thermistor shorts or opens during
compressor running.
Lighting
Once
Lighting
Twice
Lighting
3 times
Lighting
4 times
Lighting
9 times
Once
Goes out 40 A current fl ows into intelligent power
module.
9 times
Goes out Waveform of compressor current is dis-
torted.
Lighting
Lighting
Discharge temperature exceeds 114 °C
during operation.
Compressor can restart if discharge
temperature thermistor reads 100 °C or
less 3 minutes later.
Lighting
Lighting
High-pressure is detected with the
high-pressure switch (HPS) during op-
eration.
The outdoor heat exchanger tempera-
ture exceeds 70 °C during cooling or
the indoor gas pipe temperature ex-
ceeds 70°C during heating.
3 times
Goes out The fin temperature exceeds 110 °C
during operation.
4 times
Goes out The P.C. board temperature exceeds
95 °C during operation.
Lighting
Lighting The fan motor speed is 50 rpm or less
or 1500 rpm or more for 1 minute, or
the fan motor speed is 100 rpm or
less for 15 seconds when the outside
temperature is 20 °C or more.
Lighting
5 times
Nonvolatile memory data cannot be
read properly.
Lighting
Lighting
The frequency of the compressor is
kept 80Hz or more and the discharge
temperature is kept under 50 °C (cool-
ing)/40 °C (heating) for more than 40
minutes.
75
Condition
• Check the connection of
the compressor connecting
wire.
• Refer to 11-6.
check inverter/compressor.
• Check the stop valve.
• Refer to 11-6.
outdoor thermistors".
• Replace the power board.
• Replace the power board.
• Refer to 11-6.
outdoor thermistors".
• Reconnect compressor con-
nector.
• Refer to 11-6.
check inverter/compressor".
• Check the stop valve.
• Refer to 11-6.
check inverter/compressor.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6.
LEV".
• Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoor unit air pas-
sage.
• Refer to 11-6.
outdoor fan motor".
• Refer to 11-6.
outdoor fan motor".
• Replace the outdoor control
P.C. board.
• Replace the power board.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-6.
LEV".
Indoor/
outdoor
unit failure
Remedy
mode
recall
function
How to
"Check of
"Check of
"How to
" How to
"Check of
"Check of
"Check of
"Check of