Mitsubishi Electric MXZ-2C30VA Service Manual page 72

Split-type air conditioners outdoor unit
Hide thumbs Also See for MXZ-2C30VA:
Table of Contents

Advertisement

Upper or left lamp of
Abnormal point
OPERATION INDICATOR
(Failure mode / protection)
lamp (Indoor unit)
Current sensor
11-time flash
Bus-bar voltage
14-time flash
Power module
Stop valve
(Closed valve)
15-time flash
LEV for drain
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4).
LED indication
(Outdoor P.C. board)
Condition
LED 1
LED 2
8 times
Goes
A short or open circuit is detected in
out
the current sensor
during compressor operating.
6 times Goes
The bus-bar voltage exceeds 430 V
out
or falls to 50 V or below during
compressor operating.
7 times Goes
There is a high possibility that the
out
power module is out of order.
Lighting
12 times
Closed valve is detected by compressor
current.
(MXZ-2C30VA, MXZ-2C40VA)
Lighting Lighting
The indoor unit detects any
abnormalities in the LEV for drain.
72
Indoor/outdoor
Remedy
unit failure mode
recall function
• Replace the power
board.
• Replace the power
board.
• Refer to 11-6.
"How to
check inverter/
compressor".
• Check the stop valve.
• Refer to 11-6.
"Check
of LEV".
• Check the drain pump of
the indoor unit.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents