Mitsubishi Electric MXZ-2C30VA Service Manual page 105

Split-type air conditioners outdoor unit
Hide thumbs Also See for MXZ-2C30VA:
Table of Contents

Advertisement

OPERATING PROCEDURE
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel
(Refer to 1).
(2) Disconnect the power supply and indoor/outdoor
connecting wire.
(3) Disconnect the connectors for outdoor fan motor.
(4) Remove the propeller nut.
(5) Remove the propeller.
(6) Remove the screws fixing the fan motor (Photo 7).
(7) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel
(Refer to 1).
(2) Disconnect the power supply and indoor/outdoor
connecting wire and remove the back panel (Refer to 1).
(3) Remove the inverter assembly (Refer to 2).
(4) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
(0 MPa).
2
(5) Detach the brazed part of the suction and the discharge pipe
connected with compressor.
(6) Remove the nuts of compressor legs.
(7) Remove the compressor.
(8) Detach the brazed part of pipes connected with 4-way valve.
Photo 6
Photo 7
Screws of the outdoor fan motor
Propeller
Photo 8
105
PHOTOS
Outdoor heat
exchanger
temperature
thermistor
Defrost
thermistor
Propeller nut
Brazed parts of 4-way valve

Hide quick links: