Conettix D6600/D6100i | Installation and Operation Guide | 9.0

9.0 Input and Output Ports

Figure 12: D6600 Back Panel Showing
Input/Output Ports
Bosch Security Systems
Fairport, NY
USA
B
A
T
T
E
R
Y
Input:
100 - 120/
220 - 240V~
50 - 60 Hz
2.5 Amps
1 – Output 1
2 – Output 2
3 – Input 2
Figure 13: D6100i Back Panel Showing
Input/Output Ports
1
2
6
5
1 – Ground 1
2 – Input 1
3 – Output 1
9.1
UPS Monitoring through CPU
Programmable Input Ports
Use the CPU programmable input port to connect the
external UPS to the D6600/D6100i for power
monitoring. Connect the monitoring port from the UPS
to matching pins on the D6600/D6100i CPU
Programmable Input/Output port (Figure 12). Wiring
must run from the receiver through the UL Listed
rack, exit the rack through a conduit connection, and
terminate at the external UPS for UL applications. Set
up the D6600/D6100i from Menu 2.2.27 CPU
Programmable Input 1 for Input 1; Menu 2.2.28
CPU Programmable Input 2 for Input 2. Refer to the
D6600/D6100i Program Entry Guide
(P/N: 4998122702) for more information.
9.1.1

Input Default Connection Configuration

The I/O ports work with dry contact outputs.
The open circuit input voltage on the input
measures between 9 V and 12 V.
16
1
2
1
2
6
3
3
4
5
4
4 – Ground 1
5 – Ground 2
6 – Input 1
3
1
2
4
4 – Output 2
5 – Input 2
6 – Ground 2
Input and Output Ports
UPS Battery OK (restore) – contacts closed
UPS Battery Low input – contacts open
You can apply other output sources to the input wiring
as long as you follow these guidelines:
The maximum input voltage allowed without
causing damage to the input is 24 VDC.
For UPS "Battery OK" (restore), the input range
must be between 0 V and 1 V.
For UPS "Battery Low," the input range must be
between 3 V and 24 V.
The programmable input voltage range
is undefined for input voltages between
1 V and 3 V. This might cause
unexpected results such as toggling
between "Battery Low" and "Battery
OK." The input should be connected to
logic level outputs.
9.1.2

Input Reverse Connection Configuration

If the input must be the opposite polarity for correct
operation, place an external transistor circuit between
the UPS output signal and the D6600 I/O input
(Figure 14).
Follow these guidelines for correct operation:
The maximum input voltage allowed without
damaging the input is 24 V.
UPS Battery OK (restore) input range from the
UPS operates between 5 V and 24 V.
UPS Battery Low input range operates between
0 V and 0.5 V
Figure 14: Input Wiring for Reverse
Configuration
1
2
3
1 – From UPS Battery OK signal 5 to 24 V
2 – 22 k to 39 k
3 – Battery Low signal 0 to 0.6V
4 – To I/O input
5 – Any general purpose NPN transistor
Bosch Security Systems, Inc. | 9/08 | 4998122704-04