D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specifi ed. Framing or fi nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Combustible Mantels
1/2 in.
Thick Wall
Sheathing
14 in.
MIN.
Figure 5.3 Clearances To Combustible Mantels Or Other
Combustibles Above Appliance
Non-combustible Mantels
1/2 IN.
Thick Wall
Sheathing
MEASUREMENT
FROM TOP OF
FIREPLACE
OPENING
Figure 5.4 Clearances To Non-Combustible Mantels Or Other
Non-Combustibles Above Appliance
Note: For non-combustible fi replace fi nish material (marble,
stone, etc) specifi cations refer to Section 13.C.
20
12 in.
MAX.
MEASUREMENT FROM TOP OF
FIREPLACE OPENING
12 IN.
MAX.
14 IN.
MIN.
1 IN.MIN.
4 IN.
MAX.
Heat & Glo • SLR32 • 2269-900 Rev. E • 4/12
Combustible Mantel Legs Or Wall Projections
Extending Past The Face Of The Fireplace
2 IN.
3 FT. MAXIMUM
MINIMUM
FIREPLACE
OPENING
6 IN.
MINIMUM
Figure 5.5 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Non-combustible Mantel Legs Or Wall Projections
Extending Past The Face Of The Fireplace
3 IN.
FIREPLACE
MINIMUM
OPENING
7 IN.
Figure 5.6 Non-Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
Front Side Finishing Detail
1/2 IN. FACTORY-SUPPLIED
NON-COMBUSTIBLE BOARD
Figure 5.7 Front Side Finishing Detail
UNLIMITED
1/2 IN.
FRAMING
NAILING TAB