IPower 2x6
f) Temperature connector
g) RS232 connector
h) 2 x Power Socket (IEC C20, max. 16A)
i) 2 x 6 Power Ports (IEC C13, max. 10A)
LED (d) Definition:
Solid red LED: Device is not connected to ethernet
Solid orange LED: Device is connected to ethernet, TCP/IP settings are not allocated
Solid green LED: Device is connected to ethernet, TCP/IP settings allocated, device is
ready to use
Status LED blinks alternately red and green: Device is in Bootloader mode
Automatic configuration by DHCP
When you first switch on your IPower 2x6 it will look for a DHCP server and request an available IP
address (for deactivation of that feature see next section).
Please check the IP address allocated to the IPower 2x6 in the DHCP server settings to make sure that
the same address is used at every reboot.
Network configuration by GBL_Conf.exe
For changing the network properties manually, the program GBL_Conf.exe is required. This tool is
available for free on our website www.LINDY.com.
GBL_Conf.exe enables you to install
firmware updates and to reset the IPower
2x6 back to its factory settings. (see
Firmware update section).
Activate bootloader mode of the IPower
2x6 and run GBL_Conf.exe (see
Bootloader mode section). The program
will automatically look for connected
devices and will display their network
configuration. If the displayed IP address
matches the factory settings
(192.168.0.2), there is either no DHCP
server available in the network or no free
IP address could be allocated. Enter a
free IP address and netmask in to the
relevant boxes, then save these changes
by clicking on Program Device → Save
Config.
Restart the IPower 2x6 by switching it off
and on again and the changes will take
effect.
Now click on Search in order to have the new network configuration displayed.
Configuration by Web interface
Go to the web page of IPower 2x6. Enter the IP address into the address line of your internet browser:
http://"IP address of IPower 2x6" and press LOGIN.
To enter the configuration menu, click on "Configuration".