FieldServer FS-8704-12 GE-EGD Manual page 20

Ge-egd (ethernet global data) driver
Hide thumbs Also See for FS-8704-12 GE-EGD:
Table of Contents

Advertisement

FS-8704-12_GE-EGD Manual
Map_Descriptors
Map_Descriptor_Name,
Data_Array_Name,
Q1,
DATA_Q,
R1,
DATA_R,
I1,
DATA_R,
R2,
DATA_R,
I2,
DATA_R,
Q2,
DATA_R,
Read the section on data types to
see how many items are being
transmitted. Note that the %Q, %I
references are actually byte
references and not bit references as
they are always produced in
multiples of 8 and are always byte
aligned.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Data_Array_Offset,
Function,
node_name,
0
Passive,
PLC90-30,
0
Passive,
PLC90-30,
0
Passive,
PLC90-30,
1
Passive,
PLC90-30,
2
Passive,
PLC90-30,
1
Passive,
PLC90-30,
Page 20 of 26
Length,
ge_producerId,
1,
1.2.3.4,
1,
1.2.3.4,
2,
1.2.3.4,
1,
1.2.3.4,
1,
1.2.3.4,
1,
1.2.3.4,
Must correspond to
These data types must
the 'Local Producer' in
correspond to the
the EGD configuration.
references in the EGD
Is not necessarily the
range configuration.
IP address of the
producer port.
ge_exchangeId,
ge_data_type,
1,
%q,
1,
%r,
1,
%u,
1,
%r,
1,
%i,
1,
%q,
These offsets must
correspond to the offsets
in the EGD configuration.
ge_offset
0
1
3
5
7
8

Advertisement

Table of Contents
loading

Table of Contents