INSTALLER SELF-TEST

Use the Installer Self-Test to check the thermostat
configurations and operation. Refer to Table 7 for a list of the
available Self-Tests.
To start the Self-Test:
NOTE: The minimum off time for compressors is bypassed
during the Installer Self-Test.
Press and hold the increase
same time until two zeros appear. All segments of the LCD will
be displayed before the two zeros appear. See Fig. 15 and 16.
Em Ht Temporary Setting
Aux Ht
Repl
Wait
Batt
System
Em HeatOffCool Auto Only
Fig. 15. LCD display of all segments.
IMPORTANT
Models with system and fan switches must set the
switches to the equipment that is being checked for
the equipment to operate.
TEST NUMBER
Fig. 16. Test number display.
Table 7. Tests available in the Installer Self-Test.
Test
Number
Self-Test Description
10-19
Heating equipment can be turned on and off.
20-29
Emergency heat (Q7100C only) equipment can
be turned on and off.
30-39
Cooling equipment can be turned on and off.
40-49
Fan equipment can be turned on and off.
60-69
Keyboard key tests.
70-79
Thermostat information including date code and
software versions are displayed.
Refer to Table 8 for the directions and results of the specific tests.
68-0163—3
and decrease
keys at the
Remote
Room
%Humid
Outdoor
Heat Cool
Fan
OnAuto
M4844
M6792A
NOTE: Press and hold the increase
together for three seconds to exit the Self-Test. The
Self-Test times out after five minutes without any key
presses.
Thermostat Information
1. Press the Information i key to access the thermostat
information.
2. Press the increase
code. The first two large digits are the month and the
third digit is the last digit of the year
(Example: 026=February 1996).
3. Press the increase
identification code. (Example: 02 = software ID code 2).
4. Press the increase
revision number (Example: 001=Revision number 1).
10
and decrease
M4864
key to display the production date
M4866
key again to display the software
M4865
key again to display the software
M6791
keys