Installer Self-Test - Honeywell T8611G Chronotherm Installation Instructions Manual

Deluxe zoning heat pump thermostat
Table of Contents

Advertisement

INSTALLER SELF-TEST

Use the Installer Self-Test to check the thermostat
operation. Refer to Table 5 for a list of the available
self-tests.
Table 5. Tests Available In Installer Self-Test.
Test
Number
System Test Description
10-19
Heating equipment can be turned on and off.
20-29
Emergency heat equipment can be turned
on and off.
30-39
Cooling equipment can be turned on and off.
40-49
Fan equipment can be turned on and off.
60 0 to
Keyboard keys test.
60 19
70-79
Thermostat information including date code
and software versions are displayed.
CAUTION
Equipment Damage Hazard.
Minimum compressor off-time is bypassed
during the Installer System Test.
Avoid cycling compress quickly.
To start the system test:
Press and hold the increase
the same time until 10 appears. All segments of the
display are displayed before the 10 appears.
See Fig. 10 and 11.
Keys to
Test
Press
Number
Heating Equipment Self-Test
Time ∆
10
11
12
11
10
Emergency Heating Equipment Self-Test
Time ∆
20
21
22
21
20
Cooling Equipment Self-Test
Time ∆
30
31
30
Fan Equipment Self-Test
Time ∆
40
T8611G CHRONOTHERM
and decrease
keys at
Table 6. Installer System Test Options.
Enter heating equipment self-test.
Stage-one heat comes on. The system fan is also energized.
Stage-two heat comes on. Stage-one heat and system fan remain on.
Stage-two heat turns off.
Stage-one heat and system fan turn off.
Change from heating to emergency heating equipment self-test.
Emergency heat and system fan come on.
Stage 2 heat comes on.
Stage 2 heat turns off.
Emergency heat and system fan turn off.
Change from heating or emergency heating to cooling equipment self-test.
Cool and system fan come on.
Cool and system fan turn off.
Change from cooling to fan equipment self- test.
®
DELUXE ZONING HEAT PUMP THERMOSTAT
Wait
Set Program
Set Day/Time
Recovery
Hold for
Filter
Em Ht
Aux Ht
Days
Mon
Tue Wed Thu Fri Sat Sun
Wake Leave Return Sleep
Fig. 11. Display of all LCD segments.
Fig. 12. Display of test number.
Refer to Table 6 for the directions and results of the
specific tests.
NOTE: Press Time ∆ to advance to the next test and
Time ∇ to go back to the previous test. Press
Run Program to exit the system test.
Description
9
Temporary Setting
AM
PM
Repl Batt
Room
Outdoor
DST
Heat
Cool
System
Em Heat
Off
Cool
Auto
Fan
On
Auto
M14559
M14612
69-1414—2

Advertisement

Table of Contents
loading

Table of Contents