Honeywell T7100D Product Data page 9

Microelectronic commercial thermostats and subbases
Table of Contents

Advertisement

T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
Mode
Number
(Press i
key
to change)
Select
Temperature
23
averaging
network
c
(T7100F only)
.
Keypad lockout
25
level (T7100F).
Heating/cooling
27
override
(T7100F only).
Deadband
30
(T7100F only).
Interstage
31
control point
(T7100F select
models only).
Minimum on
32
time
(T7100F only).
Minimum off
33
time for the
compressor.
Temperature
34
range stops in
heating
(T7100F only).
Temperature
35
range stops in
cooling
(T7100F only).
Temperature
37
display
adjustment.
Minimum off
38
times in heating
(T7100F only).
a
Available on select models.
b
Number 02 must be set to 01 to extend fan operation.
c
Number 22 must be set to 01 and remote sensor(s) must be installed.
d
Keypad lockout is enabled and disabled by DIP switch 1 on back of thermostat.
IMPORTANT
Review the settings to confirm that they match the system. Press i to exit the Installer Setup.
Table 6. Thermostat Installer Setup Options (continued) .
Factory-Setting
Display
Description
00
Temperature
averaging disabled.
0
No lockout.
00
No temperature
change when override
key pressed.
02
Heating and cooling
setpoints can be set
no closer than 2°F.
01 (Con-
Temperature has to
ventional)
change 1°F or 2°F
o r
before the system
02 (Heat
calls for the next
pump).
stage.
02
2-minute minimum on
time for heating and
cooling.
04
4-minute minimum off
time for the
compressor.
90
Highest heating
setpoint allowed.
45
Lowest cooling
setpoint allowed.
00
No difference in
displayed temperature
and actual room
temperature.
02
2 minute minimum off
time.
Other Choices
(Press
or
Display
01
Temperature averaging between
local sensor and remote sensor(s)
activated.
1-2
1—View setpoints only.
2—Lockout all keys.
01 - 15
°F the temperature setting is
changed when the override key is
pressed. Temporary is displayed.
03 - 10
Heating and cooling setpoints can
be set no closer than the chosen
value.
00 - 12
Temperature has to change the
chosen value before the system
calls for the next stage.
00 or 01 No minimum on time or 1 minute
minimum on time for heating and
cooling.
00, 01,
Minimum number of minutes
02, 03
(0 thru 5) the compressor is off
or 05
between calls for the compressor.
40 - 89
Temperature range
(1°F increments) for heating
setpoint.
46 - 99
Temperature range
(1°F increments) for cooling
setpoint.
01 - 06
01—Display adjusts to 1°F higher
than actual room temperature.
02—Display adjusts to 2°F higher
than actual room temperature.
03—Display adjusts to 3°F higher
than actual room temperature.
04—Display adjusts to 1°F lower
than actual room temperature.
05—Display adjusts to 2°F lower
than actual room temperature.
06—Display adjusts to 3°F lower
than actual room temperature.
00, 01,
Minimum number of minutes
03, 04
(0 thru 5) the heating equipment will
or 05
be off between calls for heat.
9
key to change)
Actual
Setting
Description
68-0163—3