T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
5. Press the increase
EEPROM identification code.
(Example: 222 = EEPROM ID 222).
Key to
Test
Press
Number
Heating Equipment Self-Test
10
Enter heating equipment Self-Test.
i
11
Stage-one heat turns on. When Installer Setup number 01 is 01 or 02 is 01, the system fan is
also energized.
12
Stage-two heat turns on. Stage-one heat and system fan remain on.
13
Stage-three heat turns on. Stage-one and stage-two heat remain on.
12
Stage-three heat turns off.
11
Stage-two heat turns off.
10
Stage-one heat and system fan turn off.
Emergency Heating Equipment Self-Test (with select models of Q7100C subbase)
20
Change from heating to emergency heating equipment Self-Test.
i
21
Emergency heat turns on. System fan also turns on.
20
Emergency heat turns off.
Cooling Equipment Self-Test
30
Change from heating or emergency heating to cooling equipment Self-Test.
i
31
Stage-one cool and system fan turn on.
32
Stage-two cool and system fan turn on.
31
Stage-two cool and system fan turn off.
30
Stage-one cool and system fan turn off.
Fan Equipment Self-Test
40
Change from cooling to fan equipment Self-Test.
i
41
Fan turns on.
40
Fan turns off.
a
Key Test
60
Displays 2.
i
60
Displays 4.
60
Displays 3.
Override
60
Displays 5.
a
System
60
Displays 0.
a
Fan
60
Displays 1.
a
Available on select models.
key again to display the
M4867
Table 8. Installer Self-Test Options.
6. Press and hold the increase
together, until the room temperature is displayed, to exit
the Self-Test. The Self-Test times out after five minutes
without any key presses.
Description
11
and decrease
keys
68-0163—3