Unit Start-Up; Cooling Sequence Of Operation - Trane INTELLIPAK Installation Operation & Maintenance

Commercial single-zone rooftop air conditioners with cv or vav controls
Table of Contents

Advertisement

Cooling Sequence of Operation

Time delays are built into the controls to increase reliability
and performance by protecting the compressors and maxi-
mizing unit efficiency.
Sequence of Operation
Compressor Crankcase Heaters
Each compressor is equipped with a crankcase heater and
is controlled by a 600 volt auxiliary switch on the compres-
sor contactor. The proper operation of the crankcase heater
is important to maintain an elevated compessor oil tempera-
ture during the "Off" cycle to reduce oil foaming during com-
pressor starts.
When the compressor starts, the sudden reduction in crank-
case pressure causes the liquid refrigerant to boil rapidly
causing the oil to foam. This condition could damage com-
pressor bearings due to reduced lubrication and could
cause compressor mechanical failures.
When power has been "Off" for an extended period, allow
the crankcase heater to operate a minimum of 8 hours be-
fore starting the unit.
Units without an Economizer
Upon entering an "occupied" mode of operation, the RTM
receives input from the remote panel to start the supply fan.
For constant volume applications, the RTM supply fan con-
tacts K2 close which energizes the supply fan contactor
1K16. Units equipped with Inlet Guide Vanes (IGV), the fan
is delayed until the inlet guide vanes are driven to the full
closed position. When the supply fan starts, the fan proving
switch (3S68) closes, signaling the RTM that airflow has
been established. Inlet Guide Vanes will begin to drive open
(if equipped), or the VFD will begin to ramp the fan, (if
equipped).
When a cooling request is sent to the RTM from a zone
temperature sensor, the RTM evaluates the operating con-
dition of the system using the supply air temperature input
and the outdoor temperature input before sending the re-
quest to the SCM/MCM. Once the request is sent to the
SCM/MCM, the compressor module checks the compressor
protection circuit before closing "Stage 1" (K10 on SCM or
K11 on MCM). After the first functional stage has started,
the compressor module monitors the saturated refrigerant
temperature and closes the condenser fan output contact
"1A", when the saturated refrigerant temperature rises
above the "lower limit" setpoint.
Units with an Economizer
Upon entering an "occupied" mode of operation, the RTM
receives input from the remote panel to start the supply fan.
For constant volume applications, the RTM supply fan con-
tacts K2 close which energizes the supply fan contactor
1K16. Units equipped with Inlet Guide Vanes (IGV), the fan
is delayed until the inlet guide vanes are driven to the full
closed position. When the supply fan starts, the fan proving
switch (3S68) closes, signaling the RTM that airflow has
been established. The RTM opens the economizer dampers
to the specified "minimum position".
When a cooling request is sent to the RTM from the zone
temperature sensor, the RTM evaluates the operating con-
dition of the system using the supply air temperature input
and the outdoor temperature input before sending the re-
quest to the SCM/MCM for mechanical cooling. If the out-

Unit Start-Up

door conditions are suitable for cooling (temperature and
humidity are within specified setpoints), the RTM will at-
tempt to maintain the zone temperature without using any
compressors. If the zone temperature can not be main-
tained within the setpoint deadband, the RTM sends a cool-
ing request to the SCM/MCM. The compressor module
checks the compressor protection circuit before closing
"Stage 1" (K10 on SCM or K11 on MCM). After the first
functional stage has started, the compressor module moni-
tors the saturated refrigerant temperature and closes the
condenser fan output contact "1A", when the saturated re-
frigerant temperature rises above the "lower limit" setpoint.
Units with Traq
Sensor
TM
The fresh air enters the unit through the Traq
sembly and is measured by velocity pressure flow rings.
The velocity pressure flow rings are connected to a pres-
sure transducer/solenoid assembly. The solenoid is used for
calibration purposes to compensate for temperature swings
that could affect the transducer. The Ventilation Control
Module (VCM) utilizes the velocity pressure input, the RTM
outdoor air temperature input, and the minimum outside air
CFM setpoint to modify the volume (CFM) of fresh air enter-
ing the unit as the measured airflow deviates from setpoint.
When the optional temperature sensor is installed and the
Preheat function is enabled, the sensor will monitor the
combined (averaged) fresh air and return air temperatures.
As this mixed air temperature falls below the Preheat Actu-
ate Temperature Setpoint, the VCM will activate the preheat
binary output used to control a field installed heater. The
output will be deactivated when the temperature rises 5
above the Preheat Actuate Temperature Setpoint.
When the optional CO
sensor is installed and the CO
2
set is enabled, as the CO
the CO
Reset Start Value, the VCM will modify the mini-
2
mum outside air CFM setpoint to increase the amount of
fresh air entering the unit. The setpoint will be adjusted up-
ward until the CO
Maximum Reset Value is reached. The
2
maximum effective (reset) setpoint value for fresh air enter-
ing the unit is limited to the systems operating CFM. As the
CO
concentration decreases, the effective (reset) setpoint
2
value is adjusted downward toward the minimum outside air
CFM setpoint.
Frostat
Control
TM
The compressor module utilizes an evaporator temperature
sensor (3RT14 & 15), mounted on the suction line of each
circuit, to protect the evaporator from freezing. If the evapo-
rator temperature approaches the specified setpoint, adjust-
able between 25 F and 35 F, the compressor(s) will be
cycled "off". The compressors will not be allowed to restart
until the evaporator temperature has risen 10 F above the
specified cutout temperature and the compressor(s) have
been off for a minimum of three minutes.