Permissible Operating Voltage; Minimum Load Current - Siemens 340 Manual

Load feeders and motor starters
Table of Contents

Advertisement

4.2.5

Permissible operating voltage

To be able to ensure safe isolation of the circuits from each other in accordance with IEC
60947-1, the following operating voltages are permissible:
Table 4- 1
Control circuit
(A1/A2, OUT, IN1-3,
M1/M2)
Signaling contacts
(98/95/96)
Main circuit
(1L1/3L2/5L3
2T1/4T2/6T3)
4.2.6

Minimum load current

The minimum load current is 20% of the set motor current, but at least the absolute minimum
current specified in the tables below.
The minimum load current differs in the case of Standard 3RM10/3RM12 and Failsafe
3RM11/3RM13 motor starters:
Table 4- 2
Motor current
Motorized load
Resistive load
Table 4- 3
Motor current
Motorized load
Resistive load
As soon as the minimum current limit is violated, fault detection (phase failure) picks up.
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
Safe isolation of the 3RM1 motor starters
... to ...
Control circuit
(A1/A2, OUT, IN1-3,
M1/M2)
-
250 V
500 V
Minimum load current in the case of Standard 3RM10/3RM12 motor starters
0.5 A
0.05 A
0.05 A
Minimum load current in the case of Failsafe 3RM11/3RM13 motor starters
0.5 A
0.05 A
0.25 A
Signaling contacts
(98/95/96)
250 V
-
500 V
2 A
0.14 A
0.14 A
2 A
0.14 A
1 A
Configuration
4.2 Ambient conditions
Main circuit
(1L1/3L2/5L3
2T1/4T2/6T3)
500 V
500 V
-
7 A
0.6 A
0.6 A
7 A
0.6 A
3.5 A
57

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents