Connection Cross Sections - Siemens 340 Manual

Load feeders and motor starters
Table of Contents

Advertisement

9.1.6

Connection cross sections

Connectable cable cross-sections depend on the motor starter's connection system.
Connection system
Screw connection
Push-in spring-type terminals
Hybrid connection method
Control circuit realized as push-in spring-loaded
terminal and main circuit as screw terminal
The table below contains the suitable conductor cross-sections for the control circuit and
signaling contacts (= auxiliary contacts) and for the main circuit (= main contacts).
Type of the connectable
conductor cross-section
for main contacts
solid
finely stranded
with conductor end
processing
without conductor final
cutting
for auxiliary contacts
solid
finely stranded
with conductor end
processing
without conductor final
cutting
for AWG conductors
for main contacts
for auxiliary contacts
All AWG data applies to solid conductors.
1)
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
3RM1...-1....
1x (0,5 ... 4 mm²),
2x (0,5 ... 2,5 mm²)
1x (0,5 ... 2,5 mm²),
2x (0,5 ... 1,5 mm²)
1x (0,5 ... 2,5 mm²),
2x (1,0 ... 1,5 mm²)
1x (0.5 ... 2.5 mm²),
2x (0.5 ... 1 mm²)
1)
1x (20 ... 12),
2x (20 ... 14)
1x (20 ... 14),
2x (18 ... 16)
Order number
3RM1...-1AA.4
3RM1...-2AA.4
3RM1...-3AA.4
3RM1...-2....
1x (0.5 ... 4 mm²)
1x (0.5 ... 2.5 mm²)
1x (0.5 ... 4 mm²)
1x (0.5 ... 1.5 mm²),
2x (0.5 ... 1.5 mm²)
1x (0,5 ... 1,0 mm²),
2x (0,5 ... 1,0 mm²)
1x (0.5 ... 1.5 mm²),
2x (0.5 ... 1.5 mm²)
1x (20 ... 12)
1x (20 ... 16),
2x (20 ... 16)
Technical data
9.1 Motor starters
3RM1...-3....
1x (0,5 ... 4 mm²),
2x (0,5 ... 2,5 mm²)
1x (0,5 ... 2,5 mm²),
2x (0,5 ... 1,5 mm²)
1x (0.5 ... 1.5 mm²),
2x (0.5 ... 1.5 mm²)
1x (0,5 ... 1,0 mm²),
2x (0,5 ... 1,0 mm²)
1x (0.5 ... 1.5 mm²),
2x (0.5 ... 1.5 mm²)
1x (20 ... 12),
2x (20 ... 14)
1x (20 ... 16),
2x (20 ... 16)
123