4.3 Load feeders - protection against short circuit
Combining 3RM1 motor starters with miniature circuit breakers
Hazardous Voltage at the Motor
Can Cause Death, Serious Injury, or Property Damage.
Health hazard from automatic hot restart.
The safety function must be checked after every tripping of the motor starter protector (also
in the case of overload).
After every short circuit in the case of short-circuit protection according to type of
coordination 1, a 3RM1 motor starter is defective.
Replace a 3RM1 motor starter including the terminals after a short circuit in the case of
short-circuit protection according to type of coordination 1.
With 3RM11/3RM13 Failsafe motor starters, you must check the safety function in addition
to replacing the unit.
With 3RM11/3RM13 Failsafe motor starters, also check the safety function after a short
circuit in the case of short-circuit protection according to type of coordination 2.
The 3RM1 motor starters can be combined with the following miniature circuit breakers for
short circuits according to type of coordination 1:
Table 4- 6
Motor starter T
Order number
3RM1.01...
3RM1.02...
3RM1.07...
60
DANGER
Miniature circuit breakers according to type of coordination 1 for 3RM1 motor starters
with 400 V
= 40 °C
A
Rated current [A]
0,5
2,0
7,0
Short-circuit
Maximum permitted miniature circuit
current
breakers
with 400 V + 10%
Current [kA]
Order number
6
5SY4325-6
6
5SY4325-6
6
5SY4325-6
Manual, 11/2013, A5E0345285095020A/RS-AB/002
Rated current [A]
25
25
25
SIRIUS 3RM1 motor starter