Control circuit
The technical data of the control circuit depends on the control supply voltage.
Rated control supply voltage
24 V DC
110 ... 230 V AC/110 V DC
A distinction is made in the two tables between the 3RM10/3RM12 Standard motor starters
and the 3RM11/3RM13 Failsafe motor starters.
3RM10/3RM12 Standard motor starters
Type of voltage
Control supply voltage 1
at 50 Hz for AC
•
at 60 Hz for AC
•
for DC
•
Control supply voltage frequency
Operating range factor control supply
voltage rated value
for DC
•
at 50 Hz for AC
•
Control current
Input voltage at the digital input
for DC
Input voltage at the digital input
with AC
Input voltage at the digital input
with signal <1>
•
–
for DC
–
with AC
with signal <0>
•
–
with AC
–
for DC
Input current at the digital input
for signal <1>
•
with signal <0>
•
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
3RM10..-.AA0.
3RM12..-.AA0.
DC
V
-
V
-
V
24
Hz
-
0.8 ... 1.25
-
A
0.07
V
24
V
-
V
15 ... 30
V
-
V
-
V
0 ... 5
mA
11
mA
1
Order number
3RM1...-.AA0.
3RM1...-.AA1.
3RM10..-.AA1.
AC/DC
110 ... 230
110 ... 230
110
50 / 60
0.85 ... 1.1
0.85 ... 1.1
0.02
110
110 ... 230
79 ... 121
93 ... 253
0 ... 40
0 ... 40
2
0.4
Technical data
9.1 Motor starters
3RM12..-.AA1.