MAINTENANCE SCHEDULE
A
WARNING:
When servicing generator/engine components, the DC power must be turned off using either the DC
breaker or the battery swItch.
NOTE:
Use the engine hour meter gauge to log your engine hours or record your
engine hours by running time.
CHECK
HOURS OF OPERATION
SCHEDULEO
EACH
EXPLANATION OF SCHEDULED
MAINTENANCE
DAY
50
100 250 500 750 1000 1250
MAINTENANCE
Raw Waler Pumw
0
0
0
Remove the pump cover and inspect impeller, gas-
ket, cam and cover for wear.
Coolant System
0
0
Drain, flush, and refill cooling system with
appropriate antifreeze mi)(!ure compatible with
various COOling system metals.
Electric Fuel Lift Pump
0
0
0
0
0
0
Periodically check the wiring connections and
inspect the fuel line connections.
Inlet Fuel Filter
0
0
0
0
0
Replace.
DC Alternator
0
0
0
C.heck DC charge from alternator. Check the
mounting bracket; tighten electrical connections.
'Fuel Injectors
0
Check and adjust injection opening pressure and
spray condition (see ENGINE ADJUSTMENTS).
'Starter Motor
0
0
Check solenoid and motor for corrosion. Remove
and lubricate. Clean and lubricate the starter motor
pinion drive.
'Preheat Circuit
0
0
Check operation of preheat solenoid. Remove and
clean glow plugs; check resistance (4-6 ohms).
Reinstall with anti seize compound on threads.
'Engine Cylinder
0
0
Check compression pressure and timing
Compression
(see Engine Adjustments).
'Torque Cylinder Head
0
0
0
At first 50 hours, then every 500 hours
Hold-down bolts
(see ENGINE ADJUSTMENTS).
'Adjust the Valve Clearances
0
0
0
Adjust Valve Clearances
(see ENGINE ADJUSTMENTS).
'Heat Exchanger
0
Remove, have professionally cleaned and
pressure tested.
'WESTERBEKE recommends this service be performed by an authorized mechanic.
CAUTION (WESTERLINK
or
NMEA
w
2000): The electronic components in the Digital Diesels draw a very small amouJtt of amperage (milli-amps)!rom the
generator's starting battery when the unit is in a static state. This maybe as much as 50 miUi-amps!or the system ECU and 50 mitli-amps/or each display.
This can be as much as 72 amp-hours' in a months time with no generator use. It is
no~
necessary to be concerned with this slight amperage draw
dltring~
normal seasonal use. However, iflhe generator set is not to be usedfor a number a/months, stich as winter storage, it is best to disconnect the DC power
to the generator with a NMEA-2000 system or shut off the
DC
breaker
0It
the generator's control box/or a WESTERLlNK system.
NOTE:
Keep ill mind that the Westerbeke generator may be the DC power supply for the vessel's NMEA-2000 network,
-...: WESTERBEKE
Engines
&
Generators
11