Westerbeke 7.6 kw EDT Operator's Manual page 14

D·net diesel generators single phase
Table of Contents

Advertisement

DIGITAL CONTROL PANEL/LCD SEQUENCE
START SEQUENCE
With the pre-start inspection completed, press the,START
button and the automatic sequence will begin. The six
indicator lights will illuminate green and the panel will
display the following text:
,
,
. Waitlng'for operator
--
TERBEKE
Press start to
--,-Engtnes
&
Generators
.
engage generator
Pre l'Ieatlng ......
Cranking ......
7 Seconds
RUN SEQUENCE
. . . .
As the display cycles thru the engine functions, the speed
will come up to 1800 rpms-60Hz (1500 rpms,50Hz) and
the oil pressure and engine coolant will rise to their normal
readings. The functions will cycle in the following sequemce:
'Engine Speed
,COOI,"it Teinperaiure
1800RPM81C
17SF
32"..
300'
2500'
0
10~'
o
~:::::::::::::~g:R:9L~,L ~:::;;;;::::::~:R:OL:L~
Battery Voltage
on
Pressure "
3.1'
,40
13.5
VDC
'eM
PSI
o
30
"
"~o
1IIiii _ _ _
c::~,1!)'Q
o
.6~9
!::::::::::;:, . .
:_:SC:R:OL~L ~::::::::::::':SC:R:O:LL~
, AC Frequency
Engine Hours
3,8
HOURS
60.1Hz
o
100
I
::::::::===' : . .
S:C:RO:L~L
SCROLL
~
AC Phase Voltage
AC Line Voltage
ro
120V':-0
-====;;;!
SCROLL LOCK
To. stop the continuing sequence, press the
s '
':CI<~O~"L ][,(liCK
button. This enables the operator to monitor a
for any length of time. Theword LOCK will appear
com:et.
U~e,lhI' up
and
down
arrows to find arid observe other
functio\lii. To resume scrolling, press the SCROLL LOCK '
button again.
..
,
~
- -
STOP SEQUENCE
To stop the generator, press the STOP button. The display
will cycle thru the following text messages and shutdown.
Shutting'
Down "
Engine Shutdown
Waiting for operator
Press start to
engage generator
FAILURE LIGHT/SHUTDOWN
Ifa problem occurs, the generator will shutdown and the
FAILURE light will illuminate red. In addition, one of the
indicator lights will change from green to orange to reveal
where the trouble has occured and the display will text
message what has happened,
, ,
, Examples:
Failure Light
is
red.
CoQldnt
temperatlb"e'
Light
is orange. ..
, Failure Light isred.
Oil Pressure Light is orl1nge.
High Engine Temp.
Reset ECU to Restart '
Low Oil Pressure
Reset ECU to Restart
When a failure occurs, refer to the troubleshooting chart,
wiring diagram, and general operating text in this manual to
assist in solving the trouble.
There are many combinations of messages that can be
displayed but they are all self explanatory and the operator
can easily isolate and correct the problem should one occur.
Before re-starting the generator, tlie 20 amp DC circuit
br~Yl<er must be reset. With the problem cOrrected and the
generator started, the sequences will begin cycling again.