Set temp mode changeover

Limit Operation
Limit operation provides thermostat control within the range of the set minimum and maximum temperature.
The minimum temperature setting will trigger heating. The maximum temperature setting will trigger cooling.
Operation Method
1
MainMenu
Set temp mode changeover
Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info
Return
Setting
Fan
Set temperature
max
min
Return Press the menu button
Basic screen
2
Fan
Set temperature
max
min
Return Press the menu button
3
Fan
Set temperature
max
min
Return Press the menu button
English
The limit operation can not be enabled when a centralized control is connected.
Display the main menu screen.
1/2
(See page 26.)
Press
temp mode changeover" on the
main menu screen.
Pressing Menu/Enter button takes
you back to the basic screen, and
28
°C
the set temperature is displayed in
20
°C
max °C min °C.
*
To return to the normal set temperature
screen, use "Set temp mode changeover" in
the Main Menu again.
To change the set temperature,
press
28
°C
The set temperature is highlighted
20
°C
and ready to be changed.
The set temperature will increase by
1°C when the
and decrease by 1°C when the
button is pressed.
Note
The difference between the maximum and minimum
temperatures cannot be set to less than 6°C.
(* Maximum temperature – Minimum temperature ≥ 6°C)
Pressing
variable set temperature between
28
°C
max. and min.
20
°C
buttons to select "Set
(Limit Operation)
buttons.
button is pressed
buttons switches the
27