E. Combustible Mantel
See Figure 11.11.
A combustible mantel may be positioned no lower than
12 in./305 mm (I60) or 20 in./508 mm (I80) above the
top of the fi replace opening.
A combustible mantel may have a maximum depth of
12 in./305 mm.
Combustible trim and materials cannot be placed within
6 in. (152 mm) of the fi replace opening (top or sides).
Combustible materials projecting more than 1-1/2 in.
(38 mm) shall not be placed within 12 in. (305 mm) from
the top of the fi replace opening.
Combustible trim must not cover the metal surfaces of
the fi replace.
Mantel clearance is in accordance with Section 7-3.3.3
of ANSI/NFPA211.
12 in.
(305 mm)
*
Top of
Fireplace
Opening
*
I60 12 in./305 mm
I80 20 in./504 mm
Figure 11.11 Clearances to Mantels or other Combustibles above
Fireplace
44
55-1/2 in.
(1410 mm)
Effective
Height
Heatilator • I60, I80 • 4013-250 • Rev C • 11/08