D. Finishing Material
Refer to Sections 11.A. and Sections 11.B. for combus-
tible/noncombustible materials. Refer to Figure 11.9 for
noncombustible zone.
WARNING! Risk of Fire! You must maintain clearances.
Use only non-combustible framing material below
standoffs.
Sheetrock, wood or other combustibles must NOT be
used as sheathing or facing in the noncombustible
zone.
DO NOT cover metal fi replace front with combustible
materials.
Install combustible materials only to specifi ed clearances
on top front and side edges.
Finished combustible wall
Combustible material
Non-combustible
decorative facing
(up to full brick depth)
Continuous,
non-combustible sealant
Tile, stone or other
non-combustible material
HX4 Hearth Ext
or equivilent
insulation
Figure 11.10 Decorative Facing
Metal strips are placed 2 in. (51 mm)
under the front of the fireplace and must
extend beyond the front and sides of
fireplace opening by 2 in. (51 mm)
Heatilator • I60, I80 • 4013-250 • Rev C • 11/08
These surfaces
may be covered
with non-combustible
material.
Figure 11.9 Noncombustible Facing
Flat 2 x 4 stud wall
2 x 4 header, flush with
front of stand-offs
Floor constructed of wood or
other combustible material
Non-combustible
sealant.
43