Troubleshooting

11.1.4 Storage Subsystem Switches OFF

Temperature too high
The actually internal temperature (°C) of the storage subsystem can be
monitored from the server management via SES. If the temperature is higher as
42°C additionally an OverTemperature Flag will be set (which can be monitored
also via SES) and the cooling status LED on the front lights orange (see also
section "Cooling status LED lights orange" on page 73). Additionally the FFx-
RAID controller switches in the degraded mode.
If the internal temperature achieve 55°C the storage subsystem switches OFF.
Ê Wait until the storage subsystem has cooled down.
11.1.5 System will not boot after Installation of New
HDD Modules
I
HDD modules should be inserted only while the system is in operation.
Configuration incorrect (FFx-RAID controller)
Ê Call up the configuration menu and check the hard disk drives settings
(device configuration) and the additional settings (advanced configuration
options).

11.1.6 HDD READY Indicator does not light up

Ê Check whether the HDD module has been correctly installed and locked
(see section "Installing/Removing HDD/Dummy Module" on page 38).
HDD module or HDD backplane is defective
Ê Replace the HDD module. If the HDD READY indicator is still off, the
HDD backplane is defective. Contact the Service organization.
U41221-J-Z156-1-74
Problem Solutions and Tips
75