Other Tab

Figure 48. Other tab
In Rover, the Other Tab can be changed by selecting the Configure button. Following are
descriptions of each line on the Other tab. Use this tab to calibrate sensors and set up timers.
Calibration
Space Temperature Sensor: Use this area to calibrate the space temperature. The effective value
is the result of the space temperature used by the controller plus the offset value. In the Offset field,
type a negative or positive number to offset the space temperature.
Hardwired Setpoint: Use this area to calibrate the setpoint from the zone sensor. The effective
value is the result of the raw value of the hardwired setpoint plus the offset value. In the Offset field,
type a negative or positive number to add to the hardwired setpoint. After calibration, the effective
value should match the value indicated on the zone sensor thumbwheel.
Stroke Times
Primary Air Valve: Type the amount of time required to drive the air valve from fully open to fully
closed or vice versa. For field-installed VAV VV551 Controllers, this value must be changed to match
the specifications of the air valve.
Water Valve: Type the amount of time required to drive the water valve from fully open to fully
closed or vice versa. For field-installed VAV VV551 Controllers, this value must be changed to match
the specifications water valve.
Timers
Manual Override Time: Type the amount of time that the controller will remain in override. After
this time passes, air- and water-valve overrides are released automatically. Fan overrides do not
release automatically.
VAV-SVP01A-EN