Air And Water Balancing; Chapter Overview; Air Balancing - Trane VAV VV550 LonTalk Installation & Operation Manual

Microprocessor-based, direct digital controller (ddc) for the (variable air volume) vav terminal unit
Table of Contents

Advertisement

Air and Water Balancing

Chapter Overview

This chapter contains information about the following:

Air Balancing

After the unit has been mounted and all electrical and duct connections have been made, the air
distribution system should be balanced. The proper variable air volume balancing procedures
depend on the type of VAV system used and the options specified on the VariTrane unit. This section
will cover the basic balancing procedures and calibrations needed to balance an air distribution
system using VariTrane units. This section suggests only one balancing procedure. Since there are
many possible air balancing procedures, keep in mind that these procedures are only suggestions.
Note: Before performing these balancing procedures, the calibration command should be
System Checkout
System Setup
1. Drive all VAV boxes MAX.
Note: This can be done using Rover and its Air and Water Balance tool program by giving each
2. Read airflow at the most remote unit. In most systems, this will be the VAV unit located furthest
Note: To increase supply fan CFM check to make sure VFD/IGV are giving max output. If not at max
78
Air Balancing
Rover Air and Water Balancing Tool
initiated at least 15 minutes prior to the balancing procedure.
Check the VAV system installation for conformity to design.
Walk the entire system from air handling equipment to the terminal unit to determine variations
of installation from the plans.
Check for inadvertent obstructions in the ductwork (such as closed fire dampers).
Insure that any turning vanes, filters, and dampers (both volume and fire) are installed in the
correct position.
There should be a 1.5 duct diameter long run of straight ducting into the VAV units inlet.
Set the outside air dampers to their minimum position.
Start the supply and return air fan(s).
Before balancing the system, ensure that there is enough CFM for all zones.
• Starting with each individual branch duct, open all the VAV units in that branch duct to the
maximum cooling position.
VAV VV550 Controller a "Drive Max " command or by rotating the Zone sensor set point knob
to the " * " position, and hold the TOV ON button for two seconds. The damper will remain
at its maximum set point until the zone sensor knob is moved back into the normal operating
range.
from the fan. This will be the unit in the system that will be critical from an air delivery set point.
If airflow is not adequate, increase the supply fan CFM to achieve adequate airflow.
If the CFM is at or above design, the system can now be balanced. If the measured CFM is below
design, insure the VariTrane unit is in full cooling position.
If the air delivery through this VariTrane unit is still below the design requirements, increase the
supply fan CFM to achieve adequate airflow.
output; adjust discharge static setpoint until at max output. If already at max output then
VAV-SVP01A-EN