Trouble Messages - First Alert ReadyGuard-R User Manual

Hide thumbs Also See for ReadyGuard-R:
Table of Contents

Advertisement

Typical Trouble Condition Displays
To silence the beeping sound for fault conditions, press any key.
FAULT
FC
CC
dI
CA
EA
90
LOW BAT
(no zone no.)
LOW BAT
(with zone no.)
LOW BAT
Notify your
(with zone 00)
service company.
Routine Care
• Treat the components of your security system as you would any other electrical
equipment. Do not slam sensor-protected doors or windows.
• Keep dust from accumulating on the keypad and all protective sensors, particularly on
motion sensors and smoke detectors.
• The keypad and sensors should be cleaned carefully with a dry soft cloth. Do not
spray water or any other fluid on the units.
Indicates that a problem exists with the zone(s) displayed, accompanied by
rapid beeping. First, determine if the zone(s) displayed are intact and make
them so if they are not. If the zone uses a wireless detector, check that
changes in the room (moving furniture, televisions, etc.) are not blocking
wireless signals from the detector. If the problem has been corrected, the
zone descriptor(s) and FAULT should disappear from the display. If not,
key an OFF sequence (security code plus OFF) to clear the display. A fault
condition can also indicate a wiring problem. If the "FAULT" display
persists, notify your service company. Note that the system will not allow
arming if a fault condition exists. To arm the system with a fault condition
present, you must first bypass the zone(s) having the fault condition.
Indicates that a failure has occurred in the telephone communication
portion of your system or a problem with the phone line existed when
dialing was attempted.
Indicates that the control is on-line with the central station's remote
computer. The control will not operate while on-line. Wait a few minutes.
The display should disappear.
If this remains displayed for more than 1 minute, the system is disabled.
Indicates a cancelled alarm. See Entry/Exit Delay section (page 13).
Indicates an exit alarm. See Entry/Exit Delay section (page 13).
Indicates that the system has detected an RF jam condition or excessive
interference. If the condition persists, notify your service company.
Accompanied by a once-per 45 seconds beeping at the keypad, indicates
a low system battery condition exists. Refer to the procedure on the next page
to replace the system battery.
Accompanied by a once-per-45 seconds beeping at the keypad, indicates
a low battery condition exists in the wireless transmitter displayed.
Accompanied by a once-per-45 seconds beeping at the keypad, indicates
a low battery condition exists in a wireless keypad.
– 33 –

Trouble Messages

Advertisement

Table of Contents
loading

Table of Contents